Accessories

ACCESSORIES
Air dampers

Louver made of aluminum profile.

The dampers can be mounted inside, or outside of the section. The frame around the perimeter of the damper is made of galvanized steel.

Rotating mechanism – cog wheels made of polycarbonate, mounted inside the frame, protected from external environment conditions. Square rod for automatic actuator. Two rods installed if damper height is more than 1200 mm. Air tightness class 3 according to EN 1751.

Option: «Northern» execution

For the regions with the outside air temperature below -40°C provided an electric heater between the blades. Heater protects blades and cogs from icing.

Recommended accessories: BELIMO electric actuators:

  • ‰ON/OFF, or proportional 0 to 100% by 0 ... 10V signal from the automation system.
  • ‰Actuator with spring return closes the damper when power supply is off.
Flexible anti-vibration insert

 

Flexible connectors are two flanges interconnected by antvibration material. The inserts are made of galvanized steel and polyethylene tape reinforced with polyamide textile cloth.

Apply:

In unit and air ducts connections to reduce vibration in the air ducts.

Outdoor version

Additional protection from precipitation is applied to unit construction in case of outdoor execution.

  • ‰Weather hoods on the air inlets and outlets
  • ‰Protective covers for air damper actuators
  • ‰Flat or twin pitched roof

Protects the unit from external influences: water, sand, leaves, others.

Visor is equipped with a protective grid. Hood length is 300 mm. All joints are sealed.

Electric heater controller RNS

Triac controller provides smooth regulation of electric coils heating power.

Max heating power up to 75 kW (25 kW triac + two steps 25 kW each).

Pressure switch DTV 500
Pressure differential switch indicates an error in case of clogging of air filters, breaking of belts in centrifugal fans, low air flow through electric heaters, etc.
Thermal switch F3000
Duct thermostat indicates the threat of fluid freezing in water coils.
Variable frequency drive

Danfoss inverters provide smooth regulation, soft start, and active overheating protection of asynchronous fan motors.

Inverter can be supplied loose or mounted inside the fan section.

It is recommended to use VFD for both belt driven and direct driven plug
fans.

 

Water mixing set USWK
USWK controls power of water heating and cooling coils by regulating the temperature of water on coil inlet. USWK consists of 3-way valve with modulating 0-10V actuator and circulation pump.

USWK selection chart

Technical data:

    USWK
3/4-4
  USWK
3/4-6
  USWK
1-6
  USWK
1-10
  USWK
11/4-10
  USWK
11/4-16
  USWK
11/2-16
  USWK
11/2-25
  USWK
2-25
  USWK
2-40
Circulation pump   DAB VA65/180   DAB A50/180XM   DAB A56/180XM   DAB BPH 120/
250.40M
  DAB BPH 120/
280.50T
Three-way valve with
electric actuator
  Belimo
R317
  Belimo
R318
  Belimo
R322
  Belimo
R323
  Belimo
R329
  Belimo
R331
  Belimo
R338
  Belimo
R339G
  Belimo
R348
  Belimo
R349G
Three-way valve actuator   Belimo LR24A-SR   Belimo
NR24A-SR
  Belimo
SR24A-SR
  Belimo
NR24A-SR
  Belimo
SR24A-SR
Connection   Thread   Flange
Three-way valve nominal
diameter
  DN 20   DN 20   DN 25   DN 25   DN 32   DN 32   DN 40   DN 40   DN 50   DN 50
Three-way valve Kvs   4   6.3   6.3   10   10   16   16   25   25   40