NK series (rectangular)

NK series (rectangular)

Duct electric heater.


Description

Applications

Duct electrical heaters are designed for heating of intake air in rectangular ventilating system. The heaters are applied for air heating in ventilation and air conditioning systems in various premises.

Design

The casing and the terminal box are made of galvanized steel plate and the heating elements are of stainless steel. The models with the size from 400x200 to 600x350 the electric heating elements are extra ribbed to increase heat exchange surface. NK duct heaters are equipped with two overheating protection thermostats:

  • basic protection with automatic restart (operating temperature +50°С). After cooling the thermostat closes the control circuit of the heater automatically.
  • emergency protection with manual restart (operating temperature above +90°С). In case of response the power supply to the heater is allowed after the manual emergency reset only.
  • the thermostat contacts are located in the terminal box for external connection.

Each standard size has several electric power capacity options. Higher capacity can be attained by means of installation of the heaters in series. In the heaters with heating capacity above 27 kW the tubular heating elements are grouped per 9 kW each. Each group consists of three Δ connected tubular elements.

Mounting

The heater design ensures its mounting by means of flange connection. The air flow direction shall match the pointer on the filter. The duct heaters can be installed in any position except for with the electric control unit below to prevent condensate penetration and wiring short circuit.

The mounting shall be performed in such a way as to enable the uniform air stream distribution along the entire cross section.

The air filter shall be installed at the heater inlet to protect the heating elements against pollution.

We recommend to keep such distance between the heater and other system elements which is no less than the heater diagonal, i.e. the distance from one angle to another in its air passage part.

The duct heaters are designed for the minimum air flow 1.5 m/s and the operating air temperature 40 °C. In case of speed control option ensure the minimum air flow through the heater.

Power supply to the heater shall be disabled if the fan is not running.

To ensure the correct and safe heater operation the automation system can be applied to ensure the complex control and protection:

  • automatic control of heating elements capacity and air heating temperature;
  • checking filter condition by means of differential pressure sensor;
  • power supply disabling in case of the supply fan shutdown or airflow speed decrease as well as in case of the built-in overheating thermostats operation;
  • shutoff of ventilating system with blowing of electrical heating elements.

Legend

Series   Flange dimensions (WxH) [mm]   Heater power [kW]   Phase
NK   400х200; 500х250; 500х300; 600х300; 600х350; 700х400; 800х500; 900х500; 1000х500   4,5; 6; 7,5; 9; 10,5; 12; 18; 21; 24; 27; 36; 45; 54   3 - three phase

2015

Technical support

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Contact information

Ukraine, 08150, Boyarka,
st 40 years of October, 36