VENTS - manufacture of ventilation and air conditioning systems
PA 01 E Maximum capacity - 1275 m3/h. | PA 02 E Maximum capacity - 2500 m3/h. | PA 03 E Maximum capacity - 3350 m3/h. | |
Phase, [˜] | 3 | 3 | 3 |
Voltage, [V] | 400 | 400 | 400 |
Frequency, [Hz] | 50 | 50 | 50 |
Maximum fan power, [W] | 320 | 620 | 1330 |
Electric heater power, [W] | 12000 | 18000 | 21000 |
Electric heater current, [A] | 17.4 | 26 | 30 |
Fan current, [A] | 0.55 | 1.05 | 2.4 |
Total unit power, [W] | 12320 | 18620 | 22330 |
Total unit current, [A] | 17.95 | 27.05 | 32.4 |
Maximum air capacity , [m³/h] | 1275 | 2500 | 3350 |
RPM, [min -1] | 2700 | 2690 | 2730 |
Sound pressure level at 3 m, [[dBA]] | 51 | 54 | 57 |
Casing material | aluzinc | aluzinc | aluzinc |
Maximum transported air temperature, [оC] | -25 +55 | -25 +45 | -25 +45 |
Insulation | 50 mm, mineral wool | 50 mm, mineral wool | 50 mm, mineral wool |
Filter | panel filter G4 | panel filter G4 | panel filter G4 |
Connected air duct size, [mm] | 400х200 | 500х300 | 600х350 |
Weight, [kg] | 56 | 61 | 91 |
Number of water (glycol) coil rows | - | - | - |
Heater type | electric | electric | electric |
Unit size | 01 | 02 | 03 |
Number of rows in water heater | - | - | - |
ЕС- motor | no | no | no |
Type | supply | supply | supply |
Heat recovery | no | no | no |
Technical supportPhohe Customer service. +380 44 406 36 25 | Contact informationUkraine, 08150, Boyarka, st 40 years of October, 36 |