VENTS - manufacture of ventilation and air conditioning systems
VUT 350 PE EC Maximum capacity - 350 m3/h. | VUT 600 PE EC Maximum capacity - 700 m3/h. | VUT 1000 PE EC Maximum capacity - 1100 m3/h. | VUT 2000 PE EC Maximum capacity - 2000 m3/h. | VUT 3000 PE EC Maximum capacity - 4000 m3/h. | |
Phase, [˜] | 1 | 1 | 1 | 3 | 3 |
Voltage, [V] | 220-240 | 220-240 | 220-240 | 400 | 400 |
Frequency, [Hz] | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 |
Maximum fan power, [W] | 200 | 270 | 400 | 2pcs. х 420 | 2pcs. х 990 |
Electric heater power, [W] | 1500 | 2000 | 3300 | 12000 | 21000 |
Electric heater current, [A] | 6.5 | 8.7 | 14.3 | 17.4 | 30 |
Fan current, [A] | 1.62 | 1.6 | 2.26 | 2pcs. х 2.5 | 2pcs. х 1.7 |
Total unit power, [W] | 1700 | 2270 | 3700 | 12840 | 23000 |
Total unit current, [A] | 8.12 | 10.3 | 16.56 | 22.4 | 33.4 |
Maximum air capacity , [m³/h] | 350 | 700 | 1100 | 2000 | 4000 |
RPM, [min -1] | 3560 | 3060 | 2780 | 2920 | 2580 |
Sound pressure level at 3 m, [[dBA]] | 48 | 53 | 52 | 58 | 59 |
Casing material | aluzinc | aluzinc | aluzinc | aluzinc | aluzinc |
Maximum transported air temperature, [оC] | -25 +40 | -25 +60 | -25 +60 | -25 +40 | -25 +50 |
Insulation | 20 mm, mineral wool | 20 mm, mineral wool | 20 mm, mineral wool | 25 mm, mineral wool | 25 mm, mineral wool |
Connected air duct size, [mm] | 160 (150**) | 200 | 250 | 315 | 400 |
Weight, [kg] | 67 | 75 | 95 | 190 | 290 |
Heater type | electric | electric | electric | electric | electric |
Filter: extract | G4 | G4 | G4 | G4 | G4 |
Filter: supply | G4 (F7*) | G4 (F7*) | G4 (F7*) | G4 | G4 |
Heat recovery efficiency, [up to %] | 90 | 90 | 90 | 75 | 75 |
Heat exchanger type | counter-flow | counter-flow | counter-flow | cross-flow | cross-flow |
Heat exchanger material | polysterene | polysterene | polysterene | aluminium | aluminium |
ЕС- motor | yes | yes | yes | yes | yes |
EC fan supply voltage, [V] | - | - | - | - | - |
Type | air handling units with heat recovery | air handling units with heat recovery | air handling units with heat recovery | air handling units with heat recovery | air handling units with heat recovery |
Heat recovery | yes | yes | yes | yes | yes |
SEC Class | A | A | - | - | - |
Technical supportPhohe Customer service. +380 44 406 36 25 | Contact informationUkraine, 08150, Boyarka, st 40 years of October, 36 |