VS 400-4D (Υ)
Inline centrifugal sound- and heat-insulated duct fans with back-curved impeller blades. Maximum capacity - 3525 m3/h. Υ - star connection.
Parameter | Value | Unit | |
---|---|---|---|
Phase | 3 | ˜ | |
Voltage | 400 Y | V | |
Frequency | 50 / 60 | Hz | |
Current | 0.7 / 0.93 | A | |
Power consumption | 385 / 515 | W | |
RPM | 1235 / 1220 | min -1 | |
Noise level at 3 m | 47 / 49 | [dBA] | |
Maximum transported air temperature | -40 +80 / -40 +40 | оC | |
Protection rating | IP X4 | class | |
Maximum air flow capacity at cross directed | 3340 / 3525 | m³/h | |
Maximal air flow capacity at straight directed | 3110 / 3290 | m³/h | |
Weight | 39 | kg | |
Spigot size | 400 | mm | |
Number of poles | 4 |
Sizes | A |
---|---|
mm | 690 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
- Selection method:
- Performance:
- Pressure:
Duty point
- Performance:- -
- Pressure:- -
- Power:- -
- Recovery Efficiency:- -
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 73 | 57 | 63 | 64 | 67 | 68 | 62 | 59 | 52 | ||||||||||
LwA to outlet | dBA | 74 | 60 | 63 | 65 | 69 | 66 | 67 | 61 | 51 | ||||||||||
LwA to environment | dBA | 54 | 43 | 44 | 49 | 50 | 51 | 47 | 42 | 36 |
ƞ, [%] | MC | EC | N | VSD | [kW] | [A] | [m3/h] | [Pa] | [RPM] | SR | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
3~ 400Y – star connection | ||||||||||||||||||||
41.0 | А | Static | 56.5 | No | 0.335 | 0.56 | 1789 | 271 | 1390 | 1 |