PA 01 E
Parameter | Value | Unit | |
---|---|---|---|
Phase | 3 | ˜ | |
Voltage | 400 | V | |
Frequency | 50 | Hz | |
Maximum fan power | 320 | W | |
Electric heater power | 12000 | W | |
Electric heater current | 17.4 | A | |
Fan current | 0.55 | A | |
Total unit power | 12320 | W | |
Total unit current | 17.95 | A | |
Maximum air capacity | 1275 750,975 354,45 0,35445 21292,5 | m³/h CFM l/s m³/s l/m | |
RPM | 2700 | min -1 | |
Sound pressure level at 3 m | 51 | [dBA] | |
Casing material | aluzinc | ||
Maximum transported air temperature | -25 +55 | оC | |
Insulation | 50 mm, mineral wool | ||
Filter | panel filter G4 | ||
Connected air duct size | 400х200 | mm | |
Weight | 56 | kg | |
Heater type | electric | ||
Unit size | 01 | ||
ЕС- motor | no | ||
Type | supply | ||
Heat recovery | no |
Sizes | B | B1 | B2 | B3 | H | H1 | H2 | L | L1 |
---|---|---|---|---|---|---|---|---|---|
mm | 400 | 420 | 624 | 582 | 200 | 220 | 374 | 1145 | 1106 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 62 | 45 | 62 | 60 | 55 | 45 | 45 | 47 | 25 | ||||||||||
LwA to outlet | dBA | 73 | 48 | 60 | 66 | 71 | 62 | 64 | 62 | 56 | ||||||||||
LwA to environment | dBA | 47 | 22 | 40 | 47 | 44 | 30 | 32 | 29 | 19 |