Vote

Do you find our newsfeed helpful to track our events?

Keep up with us

RSS Subscribe to blog
Vents.TV

Blog messages

Go to blog

PA 02 E

PA 02 E

Compact suspended sound-insulated fan unit. Supplies fresh filtered air to the premise. Electric heater is used for the unit operation at low temperatures. Maximum capacity - 2500 m3/h.

Products in this series  (2)

  • PA 01 E

    PA 01 E

    PA 03 E

    PA 03 E

  • SKRA series

    SKRA series

  • OKW series

    OKW series

  • OKF series

    OKF series

  • USWK series

    USWK series

  • SR series (rectangular)

    SR series (rectangular)

  • VVG  series (rectangular)

    VVG series (rectangular)

  • BELIMO TF230/TF24

    BELIMO TF230/TF24

  • BELIMO LF230/LF24

    BELIMO LF230/LF24


ParameterValueUnit
Phase
3
˜
Voltage
400
V
Frequency
50
Hz
Maximum fan power
620
W
Electric heater power
18000
W
Electric heater current
26
A
Fan current
1.05
A
Total unit power
18620
W
Total unit current
27.05
A
Maximum air capacity
2500
1472,5
695
0,695
41750
m³/h
CFM
l/s
m³/s
l/m
RPM
2690
min -1
Sound pressure level at 3 m
54
[dBA]
Casing material
aluzinc
Maximum transported air temperature
-25 +45
оC
Insulation
50 mm, mineral wool
Filter
panel filter G4
Connected air duct size
500х300
mm
Weight
61
kg
Heater type
electric
Unit size
02
ЕС- motor
no
Type
supply
Heat recovery
no
PA 02 E
SizesBB1B2B3HH1H2LL1
mm50052068964630032044712501212

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Online form

Send a message center customer support.


By using this form you confirm that you have read and agree with the site condition and terms.
Send

Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 70 52 67 67 60 55 51 53 49
LwA to outlet dBA 84 56 70 81 77 76 74 74 70
LwA to environment dBA 55 35 57 62 52 48 54 52 53