Vote

How often do you use equipment selection program?

Keep up with us

RSS Subscribe to blog
Vents.TV

Blog messages

Go to blog

VUT 600 PE EC

VUT 600 PE EC

Ceiling mounted energy saving Air Handling Unit (AHU) in the sound- and heat-insulated casing with the electric heater. Maximum capacity - 700 m3/h.

Voltage / frequency:

OK

Products in this series  (4)

    • VUT 350 PE EC

      VUT 350 PE EC

      Maximum capacity - 350 m3/h.

      VUT 1000 PE EC

      VUT 1000 PE EC

      Maximum capacity - 1100 m3/h.

      VUT 2000 PE EC

      VUT 2000 PE EC

      Maximum capacity - 2000 m3/h.

      VUT 3000 PE EC

      VUT 3000 PE EC

      Maximum capacity - 4000 m3/h.

    • SR series (round)

      SR series (round)

    • KOM series

      KOM series

    • VVG series (round)

      VVG series (round)

    • USWK series

      USWK series

    • SRF series

      SRF series

    • BELIMO TF230/TF24

      BELIMO TF230/TF24

    • KR series (round)

      KR series (round)

    • BELIMO LF230/LF24

      BELIMO LF230/LF24

    * modification
    ParameterValueUnit
    Phase
    1
    ˜
    Voltage
    220-240
    V
    Frequency
    50/60
    Hz
    Maximum fan power
    270
    W
    Electric heater power
    2000
    W
    Electric heater current
    8.7
    A
    Fan current
    1.6
    A
    Total unit power
    2270
    W
    Total unit current
    10.3
    A
    Maximum air capacity
    700
    412,3
    194,6
    0,1946
    11690
    m³/h
    CFM
    l/s
    m³/s
    l/m
    RPM
    3060
    min -1
    Sound pressure level at 3 m
    53
    [dBA]
    Casing material
    aluzinc
    Maximum transported air temperature
    -25 +60
    оC
    Insulation
    20 mm, mineral wool
    Connected air duct size
    200
    mm
    Weight
    75
    kg
    Heater type
    electric
    Filter: extract
    G4
    Filter: supply
    G4 (F7*)
    Heat recovery efficiency
    90
    up to %
    Heat exchanger type
    counter-flow
    Heat exchanger material
    polysterene
    ЕС- motor
    yes
    Type
    air handling units with heat recovery
    Heat recovery
    yes
    SEC Class
    A
    VUT 600 PE EC
    Sizes∅DBB1B3B4HH1LL1
    mm19982771129434528312012381286

    E-mail

    Please, feel free to contact us.

    support@vents.ua

    Phohe

    Customer service.

    +380 44 406 36 25

    Online form

    Send a message center customer support.


    By using this form you confirm that you have read and agree with the site condition and terms.
    Send

    Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

     

    Sound-power level   Octave-frequency band [Hz]
      Hz   General   63   125   250   500   1000   2000   4000   8000
    LwA to inlet   dBA 55 35 56 53 43 47 45 37 28
    LwA to outlet dBA 65 47 60 61 61 52 51 40 30
    LwA to environment dBA 39 30 30 39 33 23 24 26 28