VC 100 Q*
Inline centrifugal fan. Maximum capacity - 210 m3/h.
Voltage / frequency: |
Products in this series (21)
* Compliant to the ErP-regulation (EC) 327/2011, the power consumption at optimum efficiency is < 125W.
Parameter | Value | Unit | |
---|---|---|---|
Voltage | 230 | V | |
Frequency | 50 | Hz | |
Current | 0.37 | A | |
Power consumption | 60 | W | |
Maximum air capacity | 210 123,69 58,38 0,05838 3507 | m³/h CFM l/s m³/s l/m | |
RPM | 2620 | min -1 | |
Noise level at 3 m | 36 | [dBA] | |
Maximum transported air temperature | -25 +55 | оC | |
Protection rating | IP X4 | class | |
Weight | 3.1 | kg | |
Spigot size | 100 | mm | |
High-powered motor | no | ||
Low-noise design | yes | ||
SEC Class | C |
Sizes | ØD | ∅d | ØD1 | H | H1 | L |
---|---|---|---|---|---|---|
mm | 98 | 6.1 | 249 | 310 | 295 | 115 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
- Selection method:
- Performance:
- Pressure:
Duty point
- Performance:- -
- Pressure:- -
- Power:- -
- Recovery Efficiency:- -
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 62 | 52 | 60 | 56 | 66 | 48 | 48 | 41 | 28 | ||||||||||
LwA to outlet | dBA | 67 | 49 | 57 | 58 | 68 | 54 | 52 | 45 | 30 | ||||||||||
LwA to environment | dBA | 55 | 19 | 16 | 23 | 40 | 39 | 42 | 30 | 19 |