VUT 300 E2V EC
*modification
Parameter | Value | Unit | |
---|---|---|---|
Phase | 1 | ˜ | |
Unit voltage | 230 | V | |
Frequency | 50 | Hz | |
Maximum fan power | 212 | W | |
Electric heater power | 2 items х 2000 | W | |
Electric heater current | 17.4 | A | |
Fan current | 1.4 | A | |
Total unit power | 4220 | W | |
Maximum unit current | 18.8 | A | |
Maximum air capacity | 300 176,7 83,4 0,0834 5010 | m³/h CFM l/s m³/s l/m | |
Sound pressure level at 3 m | 37 | [dBA] | |
Casing material | aluzinc | ||
Maximum transported air temperature | -39 +60 | оC | |
Insulation | 20 mm, mineral wool | ||
Connected air duct size | 150 | mm | |
Weight | 38 | kg | |
Filter: extract/ supply | bag type G4/G4 (F7*) (replaceable filter order code SFK 300 Е2V EC G4 / SFK 300 E2V EC F7) | ||
Heat recovery efficiency | 95 | up to % | |
Heat exchanger type | counter-flow | ||
Heat exchanger material | polysterene | ||
Duct connection | vertical | ||
ЕС- motor | yes | ||
Heat recovery | yes | ||
SEC Class | A |
Sizes | A1 | ∅D |
---|---|---|
mm | 373 | 150 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
Sound pressure level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 59 | 28 | 42 | 50 | 56 | 53 | 48 | 43 | 35 | ||||||||||
LwA to outlet | dBA | 65 | 31 | 47 | 56 | 62 | 60 | 54 | 49 | 43 | ||||||||||
LwA to environment | dBA | 52 | 26 | 39 | 45 | 50 | 37 | 42 | 36 | 18 |