NKV 100-2

NKV 100-2

Duct water heater.


Technical parameters

ParameterValueUnit
Weight
3.9
kg
Number of water coil rows
2
Round duct size
100
mm

Diagrams

How to use water heater diagrams:
Air Speed.  Starting from 950 m3/h on the air flow scale draw a vertical line 1 till the air speed axis which makes about  3.35 m/s.

  • Supply air temperature. Prolong the line 1 up to the point where it crosses the outside air temperature (blue curve), e.g. -15°C; then draw a horizontal line 2 from this point to the left till  crossing  water in/out temperature curve (90/70 °C). From this point draw a vertical line 3 to the supply air temperature axis on top of the graphic (+23°С).
  • Heating coil capacity. Prolong the line 1 up to the point where it crosses the outside air temperature indicated as red curve (e.g., -15°С) and draw a horizontal line 4 from this point to the right to the intersection of water in/out temperature curve (e.g., 90/70 °С). From this point draw a vertical line 5 up to the scale of heating coil capacity (13.5 kW).
  • Water flow. Prolong the line 6 down to water flow axis at the bottom of the graphic  (0.14 l/s).
  • Water pressure drop. Draw the line 7 from the point where line 6 crosses the black curve to the pressure drop axis. (1.5 kPa)

Sizes

NKV 100-2
∅DBHH3LL1L2L3K
993502301503003243220G 3/4''

Accessories

  • USWK series

    USWK series