NKV 600х300-2

NKV 600х300-2

Duct water heater.


Technical parameters

ParameterValueUnit
Weight
21.8
kg
Number of water coil rows
2
Rectangular duct size
600х300
mm

Diagrams

How to use water heater diagrams:

Air Speed. Starting from 2000 m3/h on the air flow scale draw a vertical line 1 till the air speed axis which makes about  3.75 m/s.

  • Supply air temperature. Prolong the line 1 up to the point where it crosses the outside air temperature (blue curve), e.g. -20°C; then draw a horizontal line 2 from this point to the left till  crossing  water in/out temperature curve (90/70 °C). From this point draw a vertical line 3 to the supply air temperature axis on top of the graphic (+20°С).
  • Heating coil capacity. Prolong the line 1 up to the point where it crosses the outside air temperature indicated as red curve (e.g., -20°С) and draw a horizontal line 4 from this point to the right to the intersection of water in/out temperature curve (e.g., 90/70 °С). From this point draw a vertical line 5 up to the scale of heating coil capacity (37.0 kW).
  • Water discharge. Prolong the line 5 down to water discharge axis at the bottom of the graphic 6 (0.46 l/s).
  • Water pressure drop. Draw the line 7 from the point where line 6 crosses the black curve to the pressure drop axis (6.7 kPa).

Sizes

NKV 600х300-2
BB1B2B3HH1H2H3LL1L2K
6006206407653003203402502004343G 1''

Accessories