Vote

Is our site helpful for your business development?

Keep up with us

RSS Subscribe to blog
Vents.TV

Blog messages

Go to blog

NKV 800x500-2

NKV 800x500-2

Duct water heater.

  • USWK series

    USWK series


ParameterValueUnit
Weight
36.5
kg
Number of water coil rows
2
Rectangular duct size
800х500
mm
NKV 800x500-2
SizesBB1B2B3HH1H2H3LL1L2K
mm8008208409655005205404502003647G 1''

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Online form

Send a message center customer support.


By using this form you confirm that you have read and agree with the site condition and terms.
Send

How to use water heater diagrams:

Air Speed. Starting from 5500 m3/h on the air flow scale draw a vertical line 1 till the air speed axis. It makes 3.8 m/s.

  • Supply air temperature. Prolong the line 1 up to the point where it crosses the outside air temperature (blue curve), e.g. -10°C; then draw a horizontal line 2 from this point to the left till  crossing  water in/out temperature curve (90/70 °C). From this point draw a vertical line 3 to the supply air temperature axis on top of the graphic (+24.5°С).
  • Heating coil capacity. Prolong the line 1 up to the point where it crosses the outside air temperature indicated as red curve (e.g., -10°С) and draw a horizontal line 4 from this point to the right to the intersection of water in/out temperature curve (e.g., 90/70 °С). From this point draw a vertical line 5 up to the scale of heating coil capacity (73.0 kW).
  • Water discharge. Prolong the line 5 down to water discharge axis at the bottom of the graphic 6 (0.9 l/s).
  • Water pressure drop. Draw the line 7 from the point where line 6 crosses the black curve to the pressure drop axis (11.0 kPa).