Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 53 | 41 | 43 | 53 | 51 | 47 | 44 | 44 | 36 | ||||||||||
LwA to outlet | dBA | 70 | 48 | 49 | 57 | 68 | 65 | 63 | 58 | 51 | ||||||||||
LwA to environment | dBA | 45 | 29 | 32 | 37 | 40 | 27 | 29 | 26 | 27 |
VENTS - manufacture of ventilation and air conditioning systems
KSB 200 S
Compact inline sound- and heat-insulated centrifugal fan with back-curved impeller blades. Maximum capacity - 960 m3/h. |
Technical parameters
Parameter | Value | Unit | |
---|---|---|---|
Phase | 1 | ˜ | |
Voltage | 220-240 | V | |
Frequency | 50 / 60 | Hz | |
Current | 0.85 / 1.02 | A | |
Power consumption | 195 / 232 | W | |
Maximum air capacity | 950 / 960 559,55 / 565,44 264,1 / 266,88 0,2641 / 0,26688 15865 / 16032 | m³/h CFM l/s m³/s l/m | |
RPM | 2570 / 2690 | min -1 | |
Noise level at 3 m | 41 / 42 | [dBA] | |
Maximum transported air temperature | -25 +55 | оC | |
Protection rating | IP X4 | class | |
Weight | 12 | kg | |
Spigot size | 200 | mm | |
SEC Class | B |
Diagrams
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 53 | 41 | 43 | 53 | 51 | 47 | 44 | 44 | 36 | ||||||||||
LwA to outlet | dBA | 70 | 48 | 49 | 57 | 68 | 65 | 63 | 58 | 51 | ||||||||||
LwA to environment | dBA | 45 | 29 | 32 | 37 | 40 | 27 | 29 | 26 | 27 |
Sizes
|
Technical supportPhohe Customer service. +380 44 406 36 25 | Contact informationUkraine, 08150, Boyarka, st 40 years of October, 36 |