NKD 160-1.7-1

NKD 160-1.7-1

Duct heater for supply air postheating with external control. Heater power - 1,7 kW.


ParameterValueUnit
Minimum air capacity
109
m³/h
Current
7.4
A
Power
1700
W
Weight
2.5
kg
NKD 160-1.7-1
Sizes∅DBHLL1
mm159175293306190

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Online form

Send a message center customer support.


By using this form you confirm that you have read and agree with the site condition and terms.
Send
  • Selection method:
  • Performance:
  • Pressure:
Duty point
  • Performance:- -
  • Pressure:- -
  • Power:- -
  • Recovery Efficiency:- -

The NKD heater parameters calculation example:

  • It is necessary to select a heater for supply air post-heating to a temperature of +24 °C, provided the temperature downstream of the heat exchanger is +17 °C. Therefore, it is essential to increase temperature by 7 °C. The ventilation system incorporates the VENTS VUT 350 VB EC A19 air handling unit. The rated air capacity is 400 m3/h. Determine the intersection of the post-heating temperature line (+7 °C) and the rated air capacity line (400 m3/h).
  • In this case the 1200 W heater capacity provides necessary post-heating (+7 °C). The NKD heater 160-1.2-1 kW with the diameter matching the spigot diameter of the air handling unit VUT 350 VB EC A19 is a suitable model.