OKW1 600х350-3
Duct water cooler.
Products in this series (8)
Parameter | Value | Unit | |
---|---|---|---|
Casing material | galvanized steel | ||
Rectangular duct size | 600х350 | mm | |
Weight | 17 | kg |
Sizes | B | B1 | B2 | H | H1 | H2 | H3 | H4 | L | K |
---|---|---|---|---|---|---|---|---|---|---|
mm | 600 | 620 | 780 | 350 | 370 | 420 | 268 | 229 | 56 | G 3/4'' |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
How to use water cooler diagrams:
Air Speed. Starting from 2850 m3/h on the air flow scale draw a vertical line 1 till the air speed axis. It makes 3.85 m/s.
- Supply air temperature. Prolong the line 1 up to the point where it crosses the outside air temperature (e.g. +32°C); then draw a horizontal line 2 from this point to the left till crossing the outside air humidity (e.g. 50%). From this point draw a vertical line 3 to the supply air temperature at cooler outlet axis on top of the graphic (+20.7°C).
- Cooling capacity. Prolong the line 1 up to the point where it crosses the outside air temperature (e.g. +32°C) and draw a horizontal line 4 from this point to the right until it crosses the outside air humidity curve (e.g., 50%), from here draw a vertical line 5 up to the scale representing the cooling capacity (19.8 kW).
- Water flow. Prolong the line 5 down to water flow axis at the bottom of the graphic 6 (0.78 l/s).
- Water pressure drop. Draw the line 7 from the point where the line 6 crosses the black curve to the pressure drop axis(30.0 kPa).