PVZ 600x350

PVZ 600x350

Air curtain is designed against cold or hot air stream penetration into door or window openings. Maximum capacity - up to 4000 m3/h.

Products in this series  (3)

  • PVZ 700x400

    PVZ 700x400

    PVZ 800х500

    PVZ 800х500

    PVZ 900x500

    PVZ 900x500


ParameterValueUnit
Voltage
400
V
Fan power
2460
W
Fan current
3.93
A
Air capacity
4000
2356
1112
1,112
66800
m³/h
CFM
l/s
m³/s
l/m
Phase
3
˜
Electric heater power
21000
W
Electric heater current
30
A
Fan type
Filter type
Type of water heater
Type of electric heater
PVZ 600x350
SizesBH1LH2 (air curtain without heating)H2 (air curtain with water heating)H2 (air curtain with electric heater)
mm600from 2.0 to 5.0350115013501350

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Online form

Send a message center customer support.


By using this form you confirm that you have read and agree with the site condition and terms.
Send

Air curtain selection procedure

  • Determine the required air curtain orientation (e.g., vertical).
  • Determine the required heating type (W - water type, E - electrical type, N - no heating)
  • The nomographic chart 1 shows the effective reach distance of the curtain (1) (e.g., 3.5 m; for vertical orientation that value is equal to the door opening width). 
  • For the outlet air stream speed from the curtain draw a perpendicular line down to the nomographic chart 2 (e.g., 13.9 m/s).
  • Using the nomographic chart 3 determine the outlet slit of the air curtain (3) (e.g., 2.5 m; for vertical orientation that is equal to the height of the door opening). 
  • The nomographic chart 4 shows the minimum required air capacity (lines 4 and 5, e.g., 4400 m3/h). 
  • The intersection of curves 5 and 6 lies at one of the colour fields of the design  chart 5. The field of the point location detrmines the standard size of the air curtain (e.g., 800х500).
  • Projection of curve along the parable 7 up to the point of intersection with the curve that limits the colour field from above, determines the operating point of the air curtain. The air capacity 4800 m3/h which is somewhat above the minimum required air capacity refers to the effective operating point.