TT 250*
Inline mixed flow fan. Maximum capacity - 950 m3/h.
* Compliant to the ErP-regulation (EC) 327/2011, the power consumption at optimum efficiency is < 125W.
Parameter | Value | Unit | |
---|---|---|---|
Phase | 1 | ˜ | |
Voltage | 230 | V | |
Frequency | 50 / 60 | Hz | |
Current | 0.52 | A | |
Power consumption | 120 | W | |
Maximum air capacity | 950 559,55 264,1 0,2641 15865 | m³/h CFM l/s m³/s l/m | |
RPM | 1840 | min -1 | |
Noise level at 3 m | 45 | [dBA] | |
Maximum transported air temperature | 60 | оC | |
Protection rating | IP X4 | class | |
Weight | 6.9 | kg | |
Spigot size | 250 | mm | |
High-powered motor | no | ||
SEC Class | B |
Sizes | ØD | B | H | L |
---|---|---|---|---|
mm | 247 | 287 | 323 | 383 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
- Selection method:
- Performance:
- Pressure:
Duty point
- Performance:- -
- Pressure:- -
- Power:- -
- Recovery Efficiency:- -
Sound power level, A-filter applied | Sound pressure level at 3 meters, A-filter applied | Sound pressure level at 1 meters, A-filter applied | ||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Sound-power level, A - weighted | general | Octave frequency band, Hz | ||||||||||||||||||||
Hz | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | LpA, 3m [dB(A)] | LpA, 1m[dB(A)] | ||||||||||||
LwA to inlet | dB(A) | 78 | 46 | 53 | 71 | 73 | 74 | 68 | 57 | 45 | 58 | 68 | ||||||||||
LwA to outlet | dB(A) | 78 | 45 | 52 | 71 | 73 | 73 | 68 | 56 | 44 | 57 | 67 | ||||||||||
LwA to environment | dB(A) | 66 | 34 | 41 | 58 | 60 | 62 | 57 | 48 | 37 | 45 | 55 |