VENTS - manufacture of ventilation and air conditioning systems
ТТ PRO 250 EC
Maximum capacity - 1500 m3/h. |
Technical parameters
Parameter | Value | Unit | |
---|---|---|---|
Phase | 1 | ˜ | |
Frequency | 50 / 60 | Hz | |
Voltage | 230 | V | |
Current | 1.35 | A | |
Power consumption | 197 | W | |
Maximum air capacity | 1500 883,5 417 0,417 25050 | m³/h CFM l/s m³/s l/m | |
RPM | 2784 | min -1 | |
Noise level at 3 m | 53 | [dBA] | |
Maximum transported air temperature | -25 +55 | оC | |
Protection rating | IP X4 | class | |
Weight | 7.8 | kg | |
Spigot size | 250 | mm | |
SEC Class | - |
Diagrams
Sound power level, A-filter applied | Sound pressure level at 3 meters, A-filter applied | Sound pressure level at 1 meters, A-filter applied | ||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Sound-power level, A - weighted | general | Octave frequency band, Hz | ||||||||||||||||||||
Hz | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | LpA, 1m[dB(A)] | LpA, 1m[dB(A)] | ||||||||||||
LwA to inlet | dB(A) | 81 | 43 | 51 | 64 | 77 | 77 | 77 | 69 | 62 | 61 | 71 | ||||||||||
LwA to outlet | dB(A) | 81 | 49 | 54 | 67 | 75 | 78 | 77 | 72 | 62 | 61 | 71 | ||||||||||
LwA to environment | dB(A) | 73 | 53 | 49 | 56 | 66 | 71 | 68 | 55 | 43 | 53 | 63 |
Sizes
|
Technical supportPhohe Customer service. +380 44 406 36 25 | Contact informationUkraine, 08150, Boyarka, st 40 years of October, 36 |