Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 61 | 25 | 33 | 49 | 55 | 53 | 55 | 53 | 39 | ||||||||||
LwA to outlet | dBA | 59 | 35 | 36 | 51 | 55 | 55 | 55 | 50 | 42 | ||||||||||
LwA to environment | dBA | 39 | 19 | 22 | 39 | 35 | 36 | 33 | 24 | 21 |
VENTS - manufacture of ventilation and air conditioning systems
TT Silent-M 160*
Inline mixed-flow fans in sound and heat-insulated casing. Maximum capacity - 555 m3/h. |
Technical parameters
Parameter | Value | Unit | |
---|---|---|---|
Speed | min / max | ||
Phase | 1 | ˜ | |
Voltage | 230 | V | |
Frequency | 50 / 60 | Hz | |
Current | 0.2 / 0.23 | A | |
Power consumption | 45 / 52 | W | |
Maximum air capacity | 405 / 555 238,545 / 326,895 112,59 / 154,29 0,11259 / 0,15429 6763,5 / 9268,5 | m³/h CFM l/s m³/s l/m | |
RPM | 1970 / 2645 | min -1 | |
Noise level at 3 m | 26 / 33 | [dBA] | |
Maximum transported air temperature | 60 | оC | |
Protection rating | IP X4 | class | |
Weight | 6.1 | kg | |
Spigot size | 160 | mm | |
Sound- and heat-insulated casing | yes | ||
SEC Class | C |
Diagrams
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 61 | 25 | 33 | 49 | 55 | 53 | 55 | 53 | 39 | ||||||||||
LwA to outlet | dBA | 59 | 35 | 36 | 51 | 55 | 55 | 55 | 50 | 42 | ||||||||||
LwA to environment | dBA | 39 | 19 | 22 | 39 | 35 | 36 | 33 | 24 | 21 |
Sizes
|
Technical supportPhohe Customer service. +380 44 406 36 25 | Contact informationUkraine, 08150, Boyarka, st 40 years of October, 36 |