VENTS - manufacture of ventilation and air conditioning systems
VCN 160
Exhaust centrifugal fan. Maximum capacity - 685 m3/h. |
Technical parameters
Parameter | Value | Unit | |
---|---|---|---|
Voltage | 230 | V | |
Frequency | 50 / 60 | Hz | |
Current | 0.41 / 0.42 | A | |
Power consumption | 95 / 96 | W | |
Maximum air capacity | 650 / 685 382,85 / 403,465 180,7 / 190,43 0,1807 / 0,19043 10855 / 11439,5 | m³/h CFM l/s m³/s l/m | |
RPM | 2440 / 2400 | min -1 | |
Noise level at 3 m | 60 | [dBA] | |
Maximum transported air temperature | 55 | оC | |
Protection rating | IP X4 | class | |
Weight | 4.53 | kg | |
Spigot size | 160 | mm | |
SEC Class | B |
Diagrams
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 55 | 44 | 54 | 55 | 58 | 54 | 46 | 36 | 18 | ||||||||||
LwA to environment | dBA | 54 | 46 | 39 | 49 | 51 | 53 | 49 | 42 | 31 |
Sizes
|
Technical supportPhohe Customer service. +380 44 406 36 25 | Contact informationUkraine, 08150, Boyarka, st 40 years of October, 36 |