Vote

Basic parameter for domestic fan selection

Keep up with us

RSS Subscribe to blog
Vents.TV

Blog messages

Go to blog

VK 150 EC*  New product

VK 150 EC*
VK 150 EC*
  • Mounting bracket for easy installation supplied with the fan.
  • VENTS VK EC…R with a power cable.

Inline centrifugal fan. Maximum capacity - 630 m3/h.

Products in this series  (5)

    • VK 100 EC*New product

      VK 100 EC*

      Maximum capacity - 340 m3/h.

      VK 125 EC*New product

      VK 125 EC*

      Maximum capacity - 420 m3/h.

      VK 200 EC*New product

      VK 200 EC*

      Maximum capacity - 885 m3/h.

      VK 250 ECNew product

      VK 250 EC

      Maximum capacity - 1250 m3/h.

      VK 315 ECNew product

      VK 315 EC

      Maximum capacity - 1500 m3/h.

    • SR series (round)

      SR series (round)

    • FB series (round)

      FB series (round)

    • KOM series

      KOM series

    • NKV series (round)

      NKV series (round)

    • NK series (round)

      NK series (round)

    • CZ series

      CZ series

    • FBK series (round)

      FBK series (round)

    • KR series (round)

      KR series (round)

    • EC-motors regulators

      EC-motors regulators

    * Compliant to the ErP-regulation (EC) 327/2011, the power consumption at optimum efficiency is < 125W.
    ParameterValueUnit
    Phase
    1
    ˜
    Voltage
    230
    V
    Frequency
    50 / 60
    Hz
    Current
    0.63
    A
    Power consumption
    82
    W
    Maximum air capacity
    630
    371,07
    175,14
    0,17514
    10521
    m³/h
    CFM
    l/s
    m³/s
    l/m
    RPM
    3400
    min -1
    Noise level at 3 m
    50
    [dBA]
    Maximum transported air temperature
    -25 +60
    оC
    Protection rating
    IP X4
    class
    Weight
    2.5
    kg
    SEC Class
    B
    VK 150 EC*
    SizesØDØD1BLL1L2L3
    mm150300310286303030

    E-mail

    Please, feel free to contact us.

    support@vents.ua

    Phohe

    Customer service.

    +380 44 406 36 25

    Online form

    Send a message center customer support.


    By using this form you confirm that you have read and agree with the site condition and terms.
    Send
    • Selection method:
    • Performance:
    • Pressure:
    Duty point
    • Performance:- -
    • Pressure:- -
    • Power:- -
    • Recovery Efficiency:- -
    Point Power [W]
    1 82
    2 82
    3 82
    4 82
    5 54
    6 57
    7 53
    8 49
    9 32
    10 33
    11 31
    12 27
    13 17
    14 17
    15 17
    16 16
    17 9
    18 9
    19 8
    20 8
    Sound-power level   Octave-frequency band [Hz]
      Hz   Gen.   63   125   250   500   1000   2000   4000   8000
    LwA to inlet   dBA 78 55 72 69 75 70 66 59 50
    LwA to outlet dBA 77 56 71 66 71 70 66 60 50