VENTS - manufacture of ventilation and air conditioning systems
VKPF 4D 400x200
Inline centrifugal fan. Maximum capacity - 1470 m3/h. |
Technical parameters
Parameter | Value | Unit | |
---|---|---|---|
Phase | 3 | ˜ | |
Voltage | 400 | V | |
Frequency | 50 | Hz | |
Current | 0.6 | A | |
Power consumption | 282 | W | |
Maximum air capacity | 1470 865,83 408,66 0,40866 24549 | m³/h CFM l/s m³/s l/m | |
RPM | 1300 | min -1 | |
Noise level at 3 m | 52 | [dBA] | |
Maximum transported air temperature | -25 +45 | оC | |
Protection rating | IP X4 | class | |
Weight | 17.5 | kg | |
Spigot size | 400х200 | mm | |
Number of poles | 4 | ||
Sound- and heat-insulated casing | no |
Diagrams
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 72 | 56 | 69 | 65 | 57 | 58 | 57 | 53 | 48 | ||||||||||
LwA to outlet | dBA | 74 | 54 | 65 | 66 | 61 | 63 | 60 | 61 | 55 | ||||||||||
LwA to environment | dBA | 61 | 34 | 44 | 56 | 52 | 50 | 44 | 40 | 33 |
Sizes
|
Technical supportPhohe Customer service. +380 44 406 36 25 | Contact informationUkraine, 08150, Boyarka, st 40 years of October, 36 |