VENTS - manufacture of ventilation and air conditioning systems

VUE 300 H EC ECO

VUE 300 H EC ECO

Maximum capacity - 300 m3/h.


Technical parameters

ParameterValueUnit
Phase
1
˜
Unit voltage
230
V
Frequency
50/60
Hz
Max. unit power without electric heater
138
W
Max. unit current without electric heater
0.9
A
Optional electric heater power
3000
W
Optional electric heater current
13
A
Maximum air capacity
300
176,7
83,4
0,0834
5010
m³/h
CFM
l/s
m³/s
l/m
RPM
1380
min -1
Sound pressure level at 3 m
24-45
[dBA]
Casing material
aluzinc
Maximum transported air temperature
-25 +60
оC
Insulation
25 mm, mineral wool
Connected air duct size
160
mm
Weight
40
kg
Filter: extract
G4
Filter: supply
G4
Heat recovery efficiency
86-98
up to %
Heat exchanger type
counter-flow
Heat exchanger material
polysterene
ЕС- motor
yes
Type
air handling units with heat recovery
SEC Class
A

*modification

Diagrams

Point Unit single power [W]
1 83
2 96
3 124
4 134
5 45
6 48
7 60
8 73
9 20
10 22
11 25
12 27
A-weighted sound power level   Octave-frequency band [Hz]
      General   63   125   250   500   1000   2000   4000   8000 LpA, 3 m dB(A) LpA, 1 m dB(A)
LwA to supply air inlet   dB(A) 51 30 48 46 37 42 36 32 21    
LwA to supply air outlet dB(A) 61 41 54 57 55 44 46 35 24    
LwA to exhaust air inlet dB(A) 51 30 47 46 38 43 35 31 22    
LwA to exhaust air outlet dB(A) 61 40 52 58 56 43 46 34 22    
LwA surrounding dB(A) 34 23 23 32 27 19 15 19 18 24 34

Sizes

VUE 300 H EC ECO
∅DBB1B2B3HH1H2LL1
15956612539118647520211810811187

Accessories

  • SR series (round)

    SR series (round)

  • KOM series

    KOM series

  • SRF series

    SRF series

  • C series

    C series

  • NK series (rectangular)

    NK series (rectangular)

  • BELIMO TF230/TF24

    BELIMO TF230/TF24

  • BELIMO LF230/LF24

    BELIMO LF230/LF24

2015

Technical support

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Contact information

Ukraine, 08150, Boyarka,
st 40 years of October, 36