VUT 1000 EH

VUT 1000  EH

Air handling unit in sound-proof and heat-insulated casing with electric heater. Maximum capacity - 1200 m3/h.

Voltage / frequency:

OK

Products in this series  (7)

  • SR series (round)

    SR series (round)

  • KOM series

    KOM series

  • SRF series

    SRF series

  • C series

    C series

  • BELIMO TF230/TF24

    BELIMO TF230/TF24

  • BELIMO LF230/LF24

    BELIMO LF230/LF24

*option
ParameterValueUnit
Phase
3
˜
Voltage
400
V
Frequency
50
Hz
Maximum fan power
2pcs. х 410
W
Electric heater power
9000
W
Electric heater current
13
A
Fan current
2pcs. х 1.8
A
Total unit power
9800
W
Total unit current
16.6
A
Maximum air capacity
1200
706,8
333,6
0,3336
20040
m³/h
CFM
l/s
m³/s
l/m
RPM
1850
min -1
Sound pressure level at 3 m
60
[dBA]
Casing material
aluzinc
Maximum transported air temperature
-25 +40
оC
Insulation
50 mm, mineral wool
Connected air duct size
250
mm
Weight
85
kg
Heater type
electric
Filter: extract
G4
Filter: supply
G4 (F7*)
Heat recovery efficiency
78
up to %
Heat exchanger type
cross-flow
Heat exchanger material
aluminium
Duct connection
horizontal
ЕС- motor
no
Type
air handling units with heat recovery
Heat recovery
yes
SEC Class
-
VUT 1000  EH
Sizes∅DBB1B2B3HH1H2H3LL1L2
mm249613460306386698832154280107111171171

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Online form

Send a message center customer support.


By using this form you confirm that you have read and agree with the site condition and terms.
Send

Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 69 68 66 68 68 60 63 61 54
LwA to outlet dBA 70 70 73 70 65 65 62 59 58
LwA to environment dBA 49 54 55 49 51 41 37 36 33