Air handling unit in sound-proof and heat-insulated casing with electric heater. Maximum capacity - 1750 m3/h.


Technical parameters

ParameterValueUnit
Phase
3
˜
Voltage
400
V
Frequency
50/60
Hz
Maximum fan power
2pcs. х 490
W
Electric heater power
18000
W
Electric heater current
26
A
Fan current
2pcs. х 2.15
A
Total unit power
18980
W
Total unit current
30.3
A
Maximum air capacity
1750
1030,75
486,5
0,4865
29225
m³/h
CFM
l/s
m³/s
l/m
RPM
1100
min -1
Sound pressure level at 3 m
49
[dBA]
Casing material
aluzinc
Maximum transported air temperature
-25 +45
оC
Insulation
50 mm, mineral wool
Connected air duct size
315
mm
Weight
96
kg
Heater type
electric
Filter: extract
G4
Filter: supply
G4 (F7*)
Heat recovery efficiency
77
up to %
Heat exchanger type
cross-flow
Heat exchanger material
aluminium
Duct connection
horizontal
ЕС- motor
no
Type
air handling units with heat recovery
Heat recovery
yes
SEC Class
-

*option

Diagrams

Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 66 69 71 68 64 64 51 51 48
LwA to outlet dBA 69 74 71 70 62 65 63 65 56
LwA to environment dBA 43 56 59 47 44 41 35 34 30

Sizes

VUT 1500 EH
∅DBB1B2B3HH1H2H3LL1L2
314842581320520814947201595134513881445

Accessories

  • SR series (round)

    SR series (round)

  • KOM series

    KOM series

  • SRF series

    SRF series

  • C series

    C series

  • BELIMO TF230/TF24

    BELIMO TF230/TF24

  • BELIMO LF230/LF24

    BELIMO LF230/LF24

2015

Technical support

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Contact information

Ukraine, 08150, Boyarka,