Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 49 | 30 | 46 | 49 | 39 | 42 | 38 | 31 | 20 | ||||||||||
LwA to outlet | dBA | 60 | 39 | 55 | 58 | 52 | 45 | 45 | 35 | 26 | ||||||||||
LwA to environment | dBA | 34 | 20 | 23 | 30 | 27 | 18 | 18 | 20 | 21 |
VENTS - manufacture of ventilation and air conditioning systems
VUT 300-2 WH EC
Air handling unit in the sound- and heat-insulated casing with the water heating coils. Maximum capacity - 300 m3/h. |
Technical parameters
Parameter | Value | Unit | |
---|---|---|---|
Phase | 1 | ˜ | |
Voltage | 220-240 | V | |
Frequency | 50/60 | Hz | |
Maximum fan power | 2pcs. х 70 | W | |
Fan current | 2pcs. х 0.60 | A | |
Total unit power | 140 | W | |
Total unit current | 1.2 | A | |
Maximum air capacity | 300 176,7 83,4 0,0834 5010 | m³/h CFM l/s m³/s l/m | |
RPM | 1380 | min -1 | |
Sound pressure level at 3 m | 24-45 | [dBA] | |
Casing material | aluzinc | ||
Maximum transported air temperature | -25 +60 | оC | |
Insulation | 25 mm, mineral wool | ||
Connected air duct size | 160 | mm | |
Weight | 40 | kg | |
Number of water (glycol) coil rows | 2 | ||
Heater type | water | ||
Filter: extract | G4 | ||
Filter: supply | F7 (EU7) | ||
Heat recovery efficiency | 90 | up to % | |
Heat exchanger type | counter-flow | ||
Heat exchanger material | polysterene | ||
Duct connection | horizontal | ||
ЕС- motor | yes | ||
Type | air handling units with heat recovery | ||
Heat recovery | yes | ||
SEC Class | A+ |
Diagrams
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 49 | 30 | 46 | 49 | 39 | 42 | 38 | 31 | 20 | ||||||||||
LwA to outlet | dBA | 60 | 39 | 55 | 58 | 52 | 45 | 45 | 35 | 26 | ||||||||||
LwA to environment | dBA | 34 | 20 | 23 | 30 | 27 | 18 | 18 | 20 | 21 |
Sizes
|
Technical supportPhohe Customer service. +380 44 406 36 25 | Contact informationUkraine, 08150, Boyarka, st 40 years of October, 36 |