VENTS - manufacture of ventilation and air conditioning systems
VUT 300 EVK mini EC
Air handling unit in heat- and sound-insulated casing with electric heater and kitchen hood. Maximum capacity - 270 m3/h. |
Technical parameters
Parameter | Value | Unit | |
---|---|---|---|
Speed | min / max | ||
Phase | 1 | ˜ | |
Unit voltage | 220-240 | V | |
Frequency | 50/60 | Hz | |
Maximum fan power | 16 / 187 | W | |
Electric heater power | 1500 | W | |
Electric heater current | 6.5 | A | |
Fan current | 0.1 / 1.1 | A | |
Total unit power | 1690 | W | |
Total unit current | 7.6 | A | |
Maximum air capacity | 40 / 270 23,56 / 159,03 11,12 / 75,06 0,01112 / 0,07506 668 / 4509 | m³/h CFM l/s m³/s l/m | |
RPM | 1280 / 3200 | min -1 | |
Sound pressure level at 3 m | 28 / 42 | [dBA] | |
Casing material | polymer coated steel | ||
Maximum transported air temperature | -25 +60 | оC | |
Insulation | 15 mm (polypropylene foam foil) | ||
Connected air duct size | 125 | mm | |
Weight | 38 | kg | |
Filter: extract/ supply | bag type G4 / G4(F7*) (order code SFK 300 EV/EVK mini EC G4 and SFK 300 EV/ EVK mini EC F7 | ||
Heater type | electric | ||
Heat recovery efficiency | 95 | up to % | |
Heat exchanger type | counter-flow | ||
Heat exchanger material | polysterene | ||
Duct connection | vertical | ||
ЕС- motor | yes | ||
Heat recovery | yes | ||
SEC Class | A |
Diagrams
Sound pressure level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 58 | 27 | 41 | 50 | 55 | 52 | 47 | 43 | 34 | ||||||||||
LwA to outlet | dBA | 64 | 30 | 46 | 56 | 60 | 58 | 53 | 48 | 42 | ||||||||||
LwA to environment | dBA | 53 | 27 | 38 | 46 | 50 | 42 | 41 | 36 | 18 |
Sizes
Technical supportPhohe Customer service. +380 44 406 36 25 | Contact informationUkraine, 08150, Boyarka, st 40 years of October, 36 |