VENTS - manufacture of ventilation and air conditioning systems

VUT 350 PE EC

VUT 350 PE EC

Ceiling mounted energy saving Air Handling Unit (AHU) in the sound- and heat-insulated casing with the electric heater. Maximum capacity - 350 m3/h.


Technical parameters

ParameterValueUnit
Phase
1
˜
Voltage
220-240
V
Frequency
50/60
Hz
Maximum fan power
200
W
Electric heater power
1500
W
Electric heater current
6.5
A
Fan current
1.62
A
Total unit power
1700
W
Total unit current
8.12
A
Maximum air capacity
350
206,15
97,3
0,0973
5845
m³/h
CFM
l/s
m³/s
l/m
RPM
3560
min -1
Sound pressure level at 3 m
48
[dBA]
Casing material
aluzinc
Maximum transported air temperature
-25 +40
оC
Insulation
20 mm, mineral wool
Connected air duct size
160 (150**)
mm
Weight
67
kg
Heater type
electric
Filter: extract
G4
Filter: supply
G4 (F7*)
Heat recovery efficiency
90
up to %
Heat exchanger type
counter-flow
Heat exchanger material
polysterene
ЕС- motor
yes
Type
air handling units with heat recovery
Heat recovery
yes
SEC Class
A

* modification; **reducer Ø 160 to Ø 150 mm is required

Diagrams

Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 52 32 47 49 37 40 36 32 20
LwA to outlet dBA 62 39 56 58 55 48 44 36 25
LwA to environment dBA 33 20 21 31 29 21 17 20 22

Sizes

VUT 350 PE EC
∅DBB1B2B3B4HH1LL1L2
16048541559613322028513012381286925

Accessories

  • SR series (round)

    SR series (round)

  • KOM series

    KOM series

  • VVG series (round)

    VVG series (round)

  • USWK series

    USWK series

  • SRF series

    SRF series

  • BELIMO TF230/TF24

    BELIMO TF230/TF24

  • KR series (round)

    KR series (round)

  • BELIMO LF230/LF24

    BELIMO LF230/LF24

2015

Technical support

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Contact information

Ukraine, 08150, Boyarka,
st 40 years of October, 36