VUT 400 H ЕС

VUT 400 H ЕС

Sound- and heat-insulated air handling unit. It provides supply of fresh filtered air to the premise and extract of stale extract air outside. Maximum capacity - 400 m3/h.

Products in this series  (3)

  • VUT 300-1 H ЕС

    VUT 300-1 H ЕС

    VUT 300-2 H ЕС

    VUT 300-2 H ЕС

    VUT 800 H ЕС

    VUT 800 H ЕС

  • SR series (round)

    SR series (round)

  • KOM series

    KOM series

  • Speed controller R-1/010

    Speed controller R-1/010

  • SRF series

    SRF series

  • C series

    C series

  • BELIMO TF230/TF24

    BELIMO TF230/TF24

  • BELIMO LF230/LF24

    BELIMO LF230/LF24

  • CO2 sensor

    CO2 sensor

*option
ParameterValueUnit
Phase
1
˜
Unit voltage
220-240
V
Frequency
50/60
Hz
Maximum unit power
210
W
Maximum unit current
1.6
A
Maximum air capacity
400
235,6
111,2
0,1112
6680
m³/h
CFM
l/s
m³/s
l/m
RPM
2600
min -1
Sound pressure level at 3 m
30-45
[dBA]
Casing material
aluzinc
Maximum transported air temperature
-25 +60
оC
Insulation
25 mm, mineral wool
Connected air duct size
200
mm
Weight
67
kg
Filter: extract
G4
Filter: supply
G4 (F7*)
Heat recovery efficiency
98
up to %
Heat exchanger type
counter-flow
Heat exchanger material
polysterene
Duct connection
horizontal
ЕС- motor
yes
Type
air handling units with heat recovery
Heat recovery
yes
SEC Class
A
VUT 400 H ЕС
Sizes∅DBB1B2HH1H2LL1
mm200570165230540135225925830

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Online form

Send a message center customer support.


By using this form you confirm that you have read and agree with the site condition and terms.
Send

Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

Point Power, W
1 139
2 187
3 219
4 226
5 87
6 101
7 116
8 135
9 32
10 37
11 42
12 47
Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 54 32 53 52 40 44 41 37 22
LwA to outlet dBA 65 42 59 57 56 51 47 38 29
LwA to environment dBA 34 25 24 36 30 23 20 24 25