Ceiling mounted energy saving Air Handling Unit (AHU) in the sound- and heat-insulated casing with the electric heater. Maximum capacity - 700 m3/h.


Technical parameters

ParameterValueUnit
Phase
1
˜
Voltage
220-240
V
Frequency
50/60
Hz
Maximum fan power
270
W
Electric heater power
2000
W
Electric heater current
8.7
A
Fan current
1.6
A
Total unit power
2270
W
Total unit current
10.3
A
Maximum air capacity
700
412,3
194,6
0,1946
11690
m³/h
CFM
l/s
m³/s
l/m
RPM
3060
min -1
Sound pressure level at 3 m
53
[dBA]
Casing material
aluzinc
Maximum transported air temperature
-25 +60
оC
Insulation
20 mm, mineral wool
Connected air duct size
200
mm
Weight
75
kg
Heater type
electric
Filter: extract
G4
Filter: supply
G4 (F7*)
Heat recovery efficiency
90
up to %
Heat exchanger type
counter-flow
Heat exchanger material
polysterene
ЕС- motor
yes
Type
air handling units with heat recovery
Heat recovery
yes
SEC Class
A

* modification

Diagrams

 

Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 55 35 56 53 43 47 45 37 28
LwA to outlet dBA 65 47 60 61 61 52 51 40 30
LwA to environment dBA 39 30 30 39 33 23 24 26 28

Sizes

VUT 600 PE EC
∅DBB1B3B4HH1LL1
19982771129434528312012381286

Accessories

  • SR series (round)

    SR series (round)

  • KOM series

    KOM series

  • VVG series (round)

    VVG series (round)

  • USWK series

    USWK series

  • SRF series

    SRF series

  • BELIMO TF230/TF24

    BELIMO TF230/TF24

  • KR series (round)

    KR series (round)

  • BELIMO LF230/LF24

    BELIMO LF230/LF24

2015