VENTS - manufacture of ventilation and air conditioning systems

VUT 900 H EC ECO

VUT 900 H EC ECO

Maximum capacity - 940 m3/h.


Technical parameters

ParameterValueUnit
Phase
1
˜
Unit voltage
230
V
Frequency
50/60
Hz
Max. unit power without electric heater
340
W
Max. unit current without electric heater
2.2
A
Optional electric heater power
3000
W
Optional electric heater current
13
A
Maximum air capacity
940
553,66
261,32
0,26132
15698
m³/h
CFM
l/s
m³/s
l/m
RPM
1740
min -1
Sound pressure level at 3 m
28-47
[dBA]
Casing material
aluzinc
Maximum transported air temperature
-25 +60
оC
Insulation
25 mm, mineral wool
Connected air duct size
250
mm
Weight
77
kg
Filter: extract
G4
Filter: supply
G4
Heat recovery efficiency
81-98
up to %
Heat exchanger type
counter-flow
Heat exchanger material
polysterene
ЕС- motor
yes
Type
air handling units with heat recovery
SEC Class
A

*modification

Diagrams

Point Unit single power [W]
1 340
2 340
3 336
4 300
5 138
6 140
7 120
8 110
9 33
10 32
11 32
12 28
A-weighted sound power level   Octave-frequency band [Hz]
      General   63   125   250   500   1000   2000   4000   8000 LpA, 3 m dB(A) LpA, 1 m dB(A)
LwAto supply air inlet   dB(A) 36 55 51 41 47 42 38 28 29    
LwA to supply air outlet dB(A) 47 62 62 59 53 52 42 29 35    
LwAto exhaust air inlet dB(A) 36 54 51 42 48 41 37 29 29    
LwA to exhaust air outlet dB(A) 46 60 63 60 52 52 41 27 32    
LwA surrounding dB(A) 26 29 36 32 24 22 26 26 22 24 34

Sizes

VUT 900 H EC ECO
∅DBB1B2B3HH1H2LL1
24994025083734562026215612001282

Accessories

  • SR series (round)

    SR series (round)

  • KOM series

    KOM series

  • SRF series

    SRF series

  • C series

    C series

  • NK series (rectangular)

    NK series (rectangular)

  • BELIMO TF230/TF24

    BELIMO TF230/TF24

  • BELIMO LF230/LF24

    BELIMO LF230/LF24

2015

Technical support

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Contact information

Ukraine, 08150, Boyarka,
st 40 years of October, 36