VENTS - manufacture of ventilation and air conditioning systems

VUT R 1200 EH ЕС

VUT R 1200 EH ЕС

Air handling unit in sound- and heat-insulated casing with integrated electric heater. Maximum capacity - 1200 m3/h.


Technical parameters

ParameterValueUnit
Phase
3
˜
Voltage
400
V
Frequency
50/60
Hz
Maximum fan power
2 pcs. х 208
W
Electric heater power
6000
W
Total unit power
6570
W
Total unit current
9.5
A
Maximum air capacity
1200
706,8
333,6
0,3336
20040
m³/h
CFM
l/s
m³/s
l/m
RPM
1930
min -1
Sound pressure level at 3 m
60
[dBA]
Casing material
aluzinc
Maximum transported air temperature
-25 +60
оC
Insulation
20 mm, mineral wool
Connected air duct size
315
mm
Weight
165
kg
Filter: extract
G4
Filter: supply
G4 (F7*)
Heat recovery efficiency
85
up to %
Heat exchanger type
rotary
Heat exchanger material
aluminium
ЕС- motor
yes
Type
air handling units with heat recovery
Heat recovery
yes
SEC Class
-

*option

Diagrams

Calculation of air temperature at heat exchanger outlet:

t = tint+keff*(text - tint) / 100,

Where  

tint - intake air temperature 0С,      

text - extract air temperature 0С,    

keff - heat exchanger efficiency (as per diagram), %

Sizes

VUT R 1200 EH ЕС
∅DAEFGJHL
3141335373220438460880745

Accessories

  • SR series (round)

    SR series (round)

  • KOM series

    KOM series

  • VVG series (round)

    VVG series (round)

  • SRF series

    SRF series

  • C series

    C series

  • BELIMO TF230/TF24

    BELIMO TF230/TF24

  • BELIMO LF230/LF24

    BELIMO LF230/LF24

  • KRV series (round)

    KRV series (round)

2015

Technical support

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Contact information

Ukraine, 08150, Boyarka,
st 40 years of October, 36