Centrifugal roof fan VENTS VKH EC series
Centrifugal roof fans in the steel casing with the horizontal exhaust of air and the air capacity up to 11400 m3/h. Designed for exhaust ventilation systems.
Voltage / frequency: |
Products in this series (8)
Series and modification | Casing material | Turbine standard size | Motor type | |||
---|---|---|---|---|---|---|
VENTS VKH – vertical air exhaust |
_ steel with polymeric coating A – aluminum z – galvanized steel | 250; 280; 310; 355; 400; 450; 500; 560 |
ЕС – electronically commutated synchronous motor |
ErP data | |
Overall efficiency | η,[%] |
Measurement category | MC |
Efficiency category | EC |
Efficiency grade | N |
Variable speed drive | VSD |
Power | [kW] |
Current | [A] |
Air flow | [m3/h] |
Static pressure | [Pa] |
Speed | [n/min-1] |
Specific ratio | SR |
Application
The fans are rated for exhaust ventilation and air conditioning systems for various premises that require reasonable energy saving solutions and controlled ventilation systems. EC motors reduce energy demand by 1.5–3 times and ensure high performance combined with low noise operation. Such characteristics are especially important for application in public premises as banks, supermarkets, restaurants, hotels, residential premises or domestic spaces, including water pools.
Design
The fan casing is made of polymer-coated steel (VKH EC model), aluminum (VKHA EC), galvanized steel (VKHz EC).
Motor
The fans are equipped with high-efficient electronically-commutated direct current motors with external rotor and impellers with backward curved blades. EC motor is free of friction and wear parts as a commutator and brushes. These components are replaced by a maintenance-free electronic circuit board. EC motors are featured with high performance and well controllable speed range. Premium efficiency reaching 90% is a definite advantage of electronically commutated motors.
Integrated functions and control
The fan is controlled by an external 0-10 V control signal. The fan capacity is regulated depending on temperature and pressure level, smoke content, etc.
The fan has low energy consumption at any speed. Maximum fan speed does not depend on the available current frequency and is suitable for operation both at 50 and 60 Hz. Several fans can be integrated into a single computer-driven control system. Custom designed software provides high accuracy control of the fans integrated into a network. The LED-display of the computer shows all the system parameters and the operation mode can be set individually for each fan in the network.
Mounting
VKH…EC fans are designed for mounting on the roof. The mounting plate enables the fan installation on a level surface directly above a ventilation shaft or air duct and the holes on this mounting plate provide reliable rigid fixing of the fan to a static surface. While mounting the VKH...EC fans to the level surface provide a support to exclude possible water or snow ingress into an exhaust vent of the respective ventilation shaft. While installing the fan provide enough space for maintenance works.
For connection of the fans to round air ducts use the following accessories: KKV damper, GKV flexible connector, FKV counter flange. For mounting of the fans to flat surface use the mounting frame RKV.
Mounting example
VENTS VKH EC fan store roof ventilation example