USWK 1-10
Mixing set.
Products in this series (9)
Parameter | Value | Unit | |
---|---|---|---|
Three-way valve Kvs | 10 | ||
Connecting diameter | 1'' | ||
Circulating pump | DAB A50/180XM | ||
Three-way valve regulation mode | Smooth 0…10 V | ||
Three-way valve with electric actuator | Belimo R323 | ||
Three-way valve actuator | Belimo LR24A-SR | ||
Connection | Thread | ||
Three-way valve nominal diameter | DN 25 | ||
Maximum capacity | 6 3,534 1,668 0,00167 100,2 | m³/h CFM l/s m³/s l/m | |
Maximum developed head | 57 0,42921 5,814 0,22914 0,00827 | kPa mm Hg mm Aq in.wg psi | |
Pumped medium temperature | -10 +110 | оС | |
Maximum glycol content in pumped medium | 30 | % | |
Number of pump speeds | 3 | ||
Phase | 1 | ˜ | |
Maximum pump power | 184 | W | |
Pump voltage | 230 | V | |
Weight | 6.8 | kg |
Sizes | B | H | H1 | L |
---|---|---|---|---|
mm | 175 | 320 | 210 | 490 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).
To select the mixing set according to the nomographic chart, calculate the required heat medium flow through the water heat exchanger and water pressure drop (water head). These parameters are calculated according to the heating/cooling diagrams specifically for each water heat exchanger stated specifically herein.
Т1 and Т2 - supply and return pipeline;
Р1 and Р2 - manometers for supply and return pipelines in the water mains;
1 - USWK (mixing set);
2 - Water heater;
3 - Three-way valve with actuator;
4 - Circulation pump;
5 - Shutoff valve;
6 - Supply and return pipeline from water mains to the water heater;
7 - Non-return valve;
8 - Balancing valve;
9 - Coarse filter.
Thank your for your time and your wish to improve our site.