USWK 1 1/2-25

USWK 1 1/2-25

Mixing set.


ParameterValueUnit
Three-way valve Kvs
25
Connecting diameter
1 1/2"
Circulating pump

DAB BPH 120/250.40M

Three-way valve regulation mode

Smooth 0…10 V

Three-way valve with electric actuator

Belimo R339G

Three-way valve actuator

Belimo SR24A-SR

Connection
Flange
Three-way valve nominal diameter
DN 40
Maximum capacity
14
8,246
3,892
0,00389
233,8
m³/h
CFM
l/s
m³/s
l/m
Maximum developed head
110
0,8283
11,22
0,4422
0,01595
kPa
mm Hg
mm Aq
in.wg
psi
Pumped medium temperature
-10 +120
оС
Maximum glycol content in pumped medium
30
%
Number of pump speeds
3
Phase
1
˜
Maximum pump power
510
W
Pump voltage
230
V
Weight
23
kg
USWK 1 1/2-25
SizesBHH1L
mm266420255610

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Online form

Send a message center customer support.


By using this form you confirm that you have read and agree with the site condition and terms.
Send

Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

To select the mixing set according to the nomographic chart, calculate the required heat medium flow through the water heat exchanger and water pressure drop (water head). These parameters are calculated according to the heating/cooling diagrams specifically for each water heat exchanger stated specifically herein.


 

Т1 and Т2 - supply and return pipeline;
Р1 and Р2 - manometers for supply and return pipelines in the water mains;
1 - USWK (mixing set);
2 - Water heater;
3 - Three-way valve with actuator;
4 - Circulation pump;
5 - Shutoff valve;
6 - Supply and return pipeline from water mains to the water heater;
7 - Non-return valve;
8 - Balancing valve;
9 - Coarse filter.