The air handling unit in compact heat- and sound-insulated casing with vertical spigot orientation. Maximum capacity - 300 m3/h.
* option: replaceable filter, summer block
Parameter | Value | Unit | |
---|---|---|---|
Phase | 1 | ˜ | |
Unit voltage | 220-240 | V | |
Frequency | 50/60 | Hz | |
Total unit power | 167 | W | |
Total unit current | 1.13 | A | |
Maximum air capacity | 300 176,7 83,4 0,0834 5010 | m³/h CFM l/s m³/s l/m | |
RPM | 3200 | min -1 | |
Sound pressure level at 3 m | 28-47 | [dBA] | |
Casing material | polymer coated steel | ||
Maximum transported air temperature | -25 +60 | оC | |
Insulation | 20 mm, mineral wool | ||
Connected air duct size | 125 | mm | |
Weight | 23 | kg | |
Filter: extract | G4 (order code of replaceable filter SF VUT 300 V (H) mini EC Comfo G4)* | ||
Filter: supply | G4 / F7(EU7) (order code of replaceable filter SF VUT 300 V (H) mini EC Comfo G4) / SF VUT 300 V (H) mini EC Comfo F7) | ||
Summer block | order code VL VUT 300 V (H) mini EC Comfo* | ||
Heat recovery efficiency | 78 | up to % | |
Heat exchanger type | cross-flow | ||
Heat exchanger material | aluminium | ||
Duct connection | vertical | ||
ЕС- motor | yes | ||
Heat recovery | yes | ||
SEC Class | A |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
- Selection method:
- Performance:
- Pressure:
Duty point
- Performance:- -
- Pressure:- -
- Power:- -
- Recovery Efficiency:- -
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 53 | 30 | 50 | 48 | 37 | 41 | 39 | 32 | 20 | ||||||||||
LwA to outlet | dBA | 60 | 39 | 54 | 55 | 54 | 45 | 45 | 33 | 25 | ||||||||||
LwA to environment | dBA | 34 | 5 | 25 | 30 | 29 | 21 | 14 | 6 | 2 |