OKF1 700х400-3
Duct direct-expansion air cooler.
Products in this series (8)
Parameter | Value | Unit | |
---|---|---|---|
Casing material | galvanized steel | ||
Rectangular duct size | 700х400 | mm | |
Weight | 19 | kg |
Sizes | ∅D1 | ∅D2 | B | B1 | B2 | H | H1 | H2 | H3 | L |
---|---|---|---|---|---|---|---|---|---|---|
mm | 22 | 28 | 700 | 720 | 880 | 400 | 420 | 470 | 224 | 44 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
How to use freon cooler diagrams:
Air Speed. Starting from 4500 m3/h on the air flow scale draw a vertical line 1 till the air speed axis. It makes 4.7 m/s.
- Supply air temperature. Prolong the line 1 up to the point where it crosses the outside air temperature (e.g. +30°C); then draw a horizontal line 2 from this point to the left till crossing the outside air humidity (e.g. 50%). From this point draw a vertical line 3 to the supply air temperature at cooler outlet axis on top of the graphic (+22.8°C).
- Cooling coil capacity. Prolong the line 1 up to the point where it crosses the outside air temperature (e.g. +30°C) and draw a horizontal line 4 from this point to the right until it crosses the outside air humidity curve (e.g., 50%), from here draw a vertical line 5 up to the scale representing the cooling capacity (17.0 kW).
- Cooling agent discharge. Prolong the line 5 down to cooling agent discharge axis at the bottom of the graphic 6 (360 kg/hour).
- Cooling agent pressure drop. Draw the line 7 from the point where the line 6 crosses the black curve to the pressure drop axis. (19.0 kPa).