VENTS - manufacture of ventilation and air conditioning systems
VKPI 4E 600x350
Inline centrifugal sound- and heat insulated fan. Maximum capacity - 3515 m3/h. |
Technical parameters
Parameter | Value | Unit | |
---|---|---|---|
Phase | 1 | ˜ | |
Voltage | 220-240 | V | |
Frequency | 50 / 60 | Hz | |
Current | 2.37 / 3.15 | A | |
Power consumption | 470 / 700 | W | |
Maximum air capacity | 2950 / 3515 1737,55 / 2070,335 820,1 / 977,17 0,8201 / 0,97717 49265 / 58700,5 | m³/h CFM l/s m³/s l/m | |
RPM | 1370 / 1460 | min -1 | |
Noise level at 3 m | 59 | [dBA] | |
Maximum transported air temperature | -40 +80 / -40 +55 | оC | |
Protection rating | IP X4 | class | |
Weight | 56.2 | kg | |
Spigot size | 600х350 | mm | |
Number of poles | 4 | ||
Sound- and heat-insulated casing | yes |
Diagrams
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 75 | 53 | 72 | 71 | 54 | 58 | 63 | 60 | 52 | ||||||||||
LwA to outlet | dBA | 74 | 52 | 62 | 69 | 62 | 67 | 65 | 64 | 54 | ||||||||||
LwA to environment | dBA | 51 | 25 | 51 | 44 | 40 | 42 | 38 | 34 | 23 |
ƞ, [%] | MC | EC | N | VSD | [kW] | [A] | [m3/h] | [Pа] | [RPM] | SR | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
43.7 | А | Static | 58.1 | No | 0.430 | 2.17 | 1980 | 335 | 1390 | 1 |
Sizes
|
Accessories
Technical supportPhohe Customer service. +380 44 406 36 25 | Contact informationUkraine, 08150, Boyarka, st 40 years of October, 36 |