VUT 300 H EC ECO
Maximum capacity - 300 m3/h.
Voltage / frequency: |
Products in this series (11)
*modification
Parameter | Value | Unit | |
---|---|---|---|
Phase | 1 | ˜ | |
Unit voltage | 230 | V | |
Frequency | 50/60 | Hz | |
Max. unit power without electric heater | 138 | W | |
Max. unit current without electric heater | 0.9 | A | |
Optional electric heater power | 3000 | W | |
Optional electric heater current | 13 | A | |
Maximum air capacity | 300 176,7 83,4 0,0834 5010 | m³/h CFM l/s m³/s l/m | |
RPM | 1380 | min -1 | |
Sound pressure level at 3 m | 24-45 | [dBA] | |
Casing material | aluzinc | ||
Maximum transported air temperature | -25 +60 | оC | |
Insulation | 25 mm, mineral wool | ||
Connected air duct size | 160 | mm | |
Weight | 40 | kg | |
Filter: extract | G4 | ||
Filter: supply | G4 | ||
Heat recovery efficiency | 86-98 | up to % | |
Heat exchanger type | counter-flow | ||
Heat exchanger material | polysterene | ||
ЕС- motor | yes | ||
Type | air handling units with heat recovery | ||
SEC Class | A |
Sizes | ∅D | B | B1 | B2 | B3 | H | H1 | H2 | L | L1 |
---|---|---|---|---|---|---|---|---|---|---|
mm | 159 | 566 | 125 | 391 | 186 | 475 | 202 | 118 | 1081 | 1187 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
- Selection method:
- Performance:
- Pressure:
Duty point
- Performance:- -
- Pressure:- -
- Power:- -
- Recovery Efficiency:- -
Point | Unit single power [W] |
---|---|
1 | 83 |
2 | 96 |
3 | 124 |
4 | 134 |
5 | 45 |
6 | 48 |
7 | 60 |
8 | 73 |
9 | 20 |
10 | 22 |
11 | 25 |
12 | 27 |
A-weighted sound power level | Octave-frequency band [Hz] | |||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | LpA, 3 m dB(A) | LpA, 1 m dB(A) | ||||||||||||
LwA to supply air inlet | dB(A) | 51 | 30 | 48 | 46 | 37 | 42 | 36 | 32 | 21 | ||||||||||||
LwA to supply air outlet | dB(A) | 61 | 41 | 54 | 57 | 55 | 44 | 46 | 35 | 24 | ||||||||||||
LwA to exhaust air inlet | dB(A) | 51 | 30 | 47 | 46 | 38 | 43 | 35 | 31 | 22 | ||||||||||||
LwA to exhaust air outlet | dB(A) | 61 | 40 | 52 | 58 | 56 | 43 | 46 | 34 | 22 | ||||||||||||
LwA surrounding | dB(A) | 34 | 23 | 23 | 32 | 27 | 19 | 15 | 19 | 18 | 24 | 34 |
Thank your for your time and your wish to improve our site.