VUT 400 H EC ECO
Maximum capacity - 450 m3/h.
Voltage / frequency: |
Products in this series (11)
*modification
Parameter | Value | Unit | |
---|---|---|---|
Phase | 1 | ˜ | |
Unit voltage | 230 | V | |
Frequency | 50/60 | Hz | |
Max. unit power without electric heater | 306 | W | |
Max. unit current without electric heater | 2 | A | |
Optional electric heater power | 3000 | W | |
Optional electric heater current | 13 | A | |
Maximum air capacity | 450 265,05 125,1 0,1251 7515 | m³/h CFM l/s m³/s l/m | |
RPM | 2600 | min -1 | |
Sound pressure level at 3 m | 28-47 | [dBA] | |
Casing material | aluzinc | ||
Maximum transported air temperature | -25 +60 | оC | |
Insulation | 25 mm, mineral wool | ||
Connected air duct size | 200 | mm | |
Weight | 45 | kg | |
Filter: extract | G4 | ||
Filter: supply | G4 | ||
Heat recovery efficiency | 85-98 | up to % | |
Heat exchanger type | counter-flow | ||
Heat exchanger material | polysterene | ||
ЕС- motor | yes | ||
Type | air handling units with heat recovery | ||
SEC Class | A |
Sizes | ∅D | B | B1 | B2 | B3 | H | H1 | H2 | L | L1 |
---|---|---|---|---|---|---|---|---|---|---|
mm | 199 | 687 | 255 | 588 | 220 | 514 | 235 | 139 | 1092 | 1174 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
- Selection method:
- Performance:
- Pressure:
Duty point
- Performance:- -
- Pressure:- -
- Power:- -
- Recovery Efficiency:- -
Point | Unit single power [W] |
---|---|
1 | 87 |
2 | 145 |
3 | 247 |
4 | 299 |
5 | 79 |
6 | 103 |
7 | 143 |
8 | 217 |
9 | 28 |
10 | 32 |
11 | 41 |
12 | 56 |
A-weighted sound power level | Octave-frequency band [Hz] | |||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | LpA, 3 m dB(A) | LpA, 1 m dB(A) | ||||||||||||
LwA to supply air inlet | dB(A) | 32 | 50 | 51 | 40 | 43 | 40 | 37 | 25 | 29 | ||||||||||||
LwA to supply air outlet | dB(A) | 44 | 57 | 58 | 54 | 51 | 48 | 38 | 27 | 35 | ||||||||||||
LwA to exhaust air inlet | dB(A) | 32 | 49 | 51 | 41 | 44 | 39 | 36 | 26 | 29 | ||||||||||||
LwA to exhaust air outlet | dB(A) | 43 | 55 | 59 | 55 | 50 | 48 | 37 | 25 | 32 | ||||||||||||
LwA surrounding | dB(A) | 27 | 28 | 32 | 29 | 22 | 19 | 21 | 23 | 22 | 24 | 34 |
Thank your for your time and your wish to improve our site.