Vote

Basic parameter for domestic fan selection

Keep up with us

RSS Subscribe to blog
Vents.TV

Blog messages

Go to blog

VUT 500 H

VUT 500 H

Sound- and heat-insulated air handling unit. It provides supply of fresh filtered air to the premise and extract of stale extract air outside. Maximum capacity - 500 m3/h.

Voltage / frequency:

OK

Products in this series  (5)

    • VUT 350 H

      VUT 350 H

      Maximum capacity - 350 m3/h.

      VUT 530 H

      VUT 530 H

      Maximum capacity - 530 m3/h.

      VUT 600 H

      VUT 600 H

      Maximum capacity - 600 m3/h.

      VUT 1000 H

      VUT 1000 H

      Maximum capacity - 1200 m3/h.

      VUT 2000 H

      VUT 2000 H

      Maximum capacity - 2200 m3/h.

    • SR series (round)

      SR series (round)

    • KOM series

      KOM series

    • SRF series

      SRF series

    • C series

      C series

    • Switch P...-1-300

      Switch P...-1-300

    • BELIMO TF230/TF24

      BELIMO TF230/TF24

    • BELIMO LF230/LF24

      BELIMO LF230/LF24

    • Sensors

      Sensors


    ParameterValueUnit
    Phase
    1
    ˜
    Voltage
    220-240
    V
    Frequency
    50/60
    Hz
    Maximum fan power
    2pcs. x 150
    W
    Fan current
    2pcs. х 0.66
    A
    Total unit power
    300
    W
    Total unit current
    1.32
    A
    Maximum air capacity
    500
    294,5
    139
    0,139
    8350
    m³/h
    CFM
    l/s
    m³/s
    l/m
    RPM
    1100
    min -1
    Sound pressure level at 3 m
    28-47
    [dBA]
    Casing material
    aluzinc
    Maximum transported air temperature
    -25 +50
    оC
    Insulation
    25 mm, mineral wool
    Connected air duct size
    150
    mm
    Weight
    49
    kg
    Filter: extract
    G4
    Filter: supply
    F7 (EU7)
    Heat recovery efficiency
    88
    up to %
    Heat exchanger type
    cross-flow
    Heat exchanger material
    aluminium
    Duct connection
    horizontal
    ЕС- motor
    no
    Type
    air handling units with heat recovery
    Heat recovery
    yes
    SEC Class
    E
    VUT 500 H
    Sizes∅DBB1B2B3HH1H2LL1
    mm14941630054207603230148722768

    E-mail

    Please, feel free to contact us.

    support@vents.ua

    Phohe

    Customer service.

    +380 44 406 36 25

    Online form

    Send a message center customer support.


    By using this form you confirm that you have read and agree with the site condition and terms.
    Send

    Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

    Sound-power level   Octave-frequency band [Hz]
      Hz   General   63   125   250   500   1000   2000   4000   8000
    LwA to inlet   dBA 54 33 49 51 40 45 43 34 22
    LwA to outlet dBA 65 41 58 59 55 48 48 39 27
    LwA to environment dBA 37 25 26 33 29 20 19 22 23