Vote

Do you find our newsfeed helpful to track our events?

Keep up with us

RSS Subscribe to blog
Vents.TV

Blog messages

Go to blog

VUT 600 WH EC

VUT 600 WH EC

Air handling unit in the sound- and heat-insulated casing with the water heating coils. Maximum capacity - 550 m3/h.

Products in this series  (3)

  • VUT 300-1 WH EC

    VUT 300-1 WH EC

    VUT 300-2 WH EC

    VUT 300-2 WH EC

    VUT 400 WH EC

    VUT 400 WH EC

  • SR series (round)

    SR series (round)

  • KOM series

    KOM series

  • USWK series

    USWK series

  • SRF series

    SRF series

  • C series

    C series

  • BELIMO TF230/TF24

    BELIMO TF230/TF24

  • BELIMO LF230/LF24

    BELIMO LF230/LF24


ParameterValueUnit
Phase
1
˜
Voltage
220-240
V
Frequency
50/60
Hz
Maximum fan power
2pcs. x 175
W
Fan current
2pcs. х 1.3
A
Total unit power
350
W
Total unit current
2.6
A
Maximum air capacity
550
323,95
152,9
0,1529
9185
m³/h
CFM
l/s
m³/s
l/m
RPM
2150
min -1
Sound pressure level at 3 m
28-47
[dBA]
Casing material
aluzinc
Maximum transported air temperature
-25 +60
оC
Insulation
25 mm, mineral wool
Connected air duct size
200
mm
Weight
40
kg
Number of water (glycol) coil rows
2
Heater type
water
Filter: extract
G4
Filter: supply
F7 (EU7)
Heat recovery efficiency
90
up to %
Heat exchanger type
counter-flow
Heat exchanger material
polysterene
Duct connection
horizontal
ЕС- motor
yes
Type
air handling units with heat recovery
Heat recovery
yes
SEC Class
A
VUT 600 WH EC
Sizes∅DBB1B2B3HH2H3LL1L2
mm199500403161249555127231109211371198

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Online form

Send a message center customer support.


By using this form you confirm that you have read and agree with the site condition and terms.
Send

Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 59 38 56 52 41 47 44 40 24
LwA to outlet dBA 66 45 59 62 57 52 50 39 30
LwA to environment dBA 41 26 31 35 32 25 24 24 28