Vote

Are you satisfied with the site speed?

Keep up with us

RSS Subscribe to blog
Vents.TV

Blog messages

Go to blog

VUT 800 WH-4

VUT 800 WH-4

Air handling unit in sound-proof and heat-insulated casing with water heater. Maximum capacity - 780 m3/h.

  • SR series (round)

    SR series (round)

  • KOM series

    KOM series

  • USWK series

    USWK series

  • SRF series

    SRF series

  • C series

    C series

  • BELIMO TF230/TF24

    BELIMO TF230/TF24

  • BELIMO LF230/LF24

    BELIMO LF230/LF24

*option
ParameterValueUnit
Phase
1
˜
Voltage
220-240
V
Frequency
50
Hz
Maximum fan power
2pcs. х 245
W
Fan current
2pcs. х 1.08
A
Total unit power
490
W
Total unit current
2.16
A
Maximum air capacity
780
459,42
216,84
0,21684
13026
m³/h
CFM
l/s
m³/s
l/m
RPM
1650
min -1
Sound pressure level at 3 m
48
[dBA]
Casing material
aluzinc
Maximum transported air temperature
-25 +45
оC
Insulation
50 mm, mineral wool
Connected air duct size
250
mm
Weight
88
kg
Number of water (glycol) coil rows
4
Heater type
water
Filter: extract
G4
Filter: supply
G4 (F7*)
Heat recovery efficiency
78
up to %
Heat exchanger type
cross-flow
Heat exchanger material
aluminium
Duct connection
horizontal
ЕС- motor
no
Type
air handling units with heat recovery
Heat recovery
yes
SEC Class
E
VUT 800 WH-4
Sizes∅DBB1B2B3HH1H2H3LL1L2
mm249613460306386698832154280107111171171

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Online form

Send a message center customer support.


By using this form you confirm that you have read and agree with the site condition and terms.
Send

Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 56 58 56 57 59 54 50 51 44
LwA to outlet dBA 57 58 61 60 55 53 51 48 45
LwA to environment dBA 35 43 46 38 43 29 29 26 23