APPLICATIONS |
- Supply and exhaust ventilation systems for commercial, office and other public or industrial premises with limited installation space.
|
- Designed for connection with 400*200, 500*250, 500*300, 600*300, 600*350, 700*400, 800*500, 900*500, 1000*500 mm rectangular air ducts.
|
DESIGN |
- The fan casing is made of galvanized steel.
|
|
MOTOR |
-
The impeller with forward curved blades made of galvanized steel is powered by 4- or 6- pole external rotor asynchronous motor.
-
Such modification ensures high air flow capacity and relatively significant differential pressure.
-
For thermal overheating protection the thermal contacts with leaded outside terminals are incorporated in the motor winding for connection with the external protection devices.
|
- The motor is equipped with the ball bearings for long service life.
- For precise features, safe operation and low noise, each impeller is dynamically balanced while assembly.
- Motor protection rating IP 44.
|
SPEED CONTROL |
- Smooth or step speed control with a thyristor or autotransformer speed controller.
|
- Several fans may be connected to one speed controller provided that the total power and operating current do not exceed the rated speed controller parameters.
|
MOUNTING |
- The fans are designed for inline rectangular air duct mounting and require no special fixing in case of direct connection.
- In case of connection through the flexible connectors the fan is fixed to a building by means of supports, suspension brackets or fixation brackets.
- The fans can be mounted in any position with respect to the pointer direction on the casing.
|
- Access for the fan maintenance shall be provided.
- The fan is powered through the external terminals.
- The casing is provided with the removable access door for maintenance.
|
 |
VENTS VKPF fan warehouse ventilation example |