Description
- Flexible spiral seam aluminium band air ducts with high aerodynamic and strength characteristics.
Features
- Made of incombustible, corrosion-resisting aluminium band.
- Specially designed high-quality locks ensure high seam tightness and total air tightness of the ducts.
- Low dynamic losses.
- Low weight, high elasticity and easy mounting.
Recommended application
- Applied in residential and industrial ventilation, air conditioning and heating systems with the maximum pressure 10 000 Pa.
- For supply and exhaust ventilation.
Technical data:
Item | Aluvent M | Aluvent N | Aluvent S | Aluvent D |
---|---|---|---|---|
Diameter range [mm] | 80/100/110/120/125/130/140/150/160/180/200/250/315 | |||
Material | Aluminium | Aluminium | Aluminium | Aluminium |
Number of layers | 1 | 1 | 1 | 1 |
Total thickness [μm] | 50 | 80 | 100 | 2х50 |
Operating temperature range [°C] | -30 +250 | -30 +250 | -30 +250 | -30 +250 |
Maximum air speed [m/s] | 30 | 30 | 30 | 30 |
Maximum operating pressure [Pa] | 8000 | 10000 | 10000 | 10000 |
Minimum bend radius [mm] | 0.70хD | 0.73хD | 0.76хD | 0.85хD |
Length [m] | 1; 2; 2,5; 3; 6 | 1; 2; 2,5; 3; 6 | 1; 2; 2,5; 3; 6 | 1; 2; 2,5; 3; 6 |
Pressure loss diagram per 1 m stretched air duct
Calculation example:
- Select a curve that matches the air duct diameter [mm], 200 mm in this case.
- Find the intersection point of this line with the vertical line of the required air flow in m3/h, 500 m3/h in this case.
- The horizontal line that shows the pressure loss in Pa per 1 m straight air duct crosses this intersection point.
- Multiply pressure loss value (2.4 Pa/m at 20°С) by total air duct length to get the total pressure loss value. To calculate pressure loss in case of bends consider each bend as extra air duct meter.