Inline centrifugal fan VENTS VK series
Inline centrifugal fans in plastic casing with air capacity up to 1700 m3/h. Designed for supply and exhaust ventilation systems.
Voltage / frequency: |
Products in this series (26)
Fan series | Duct diameter, mm | Options | ||
---|---|---|---|---|
VENTS VK S – high-powered motor | 100; 125; 150*; 160; 200; 250; 315 |
Q – low-powered motor. U – speed controller with electronic thermostat and temperature sensor integrated into the air duct. Equipped with power cord and IEC C14 electric plug. Temperature-based operation logic. Un – speed controller with electronic thermostat and external temperature sensor fixed on 4 m cable. Equipped with power cord and IEC C14 electric plug. Temperature-based operation logic. U1 – speed controller with electronic thermostat and temperature sensor integrated into the air duct. Equipped with power cord and IEC C14 electric plug. Timer-based operation logic. U1n – speed controller with electronic thermostat and external temperature sensor fixed on 4 m cable. Equipped with power cord and IEC C14 electric plug. Timer-based operation logic. P – built-in smooth speed controller and power cord with IEC C14 electric plug. R – power cord with IEC C14 electric plug. |
* VK 150 model is compatible with the air ducts both Ø150 and Ø160 mm
Applications
VK fans are applied for supply and exhaust ventilation systems of commercial, office and other premises. Compatible with Ø 100, 125, 150, 200, 250 and 315 mm round air ducts. Models marked VK...Q are supplied with quiet motors for low-noise applications. Due to the corrosion-resistant durable plastic casing, these models are the perfect solution for the installation in exhaust ventilation systems in humid premises such as bathrooms, kitchens etc.
Design
The casing is made of high-quality durable ABS plastic. The fans are equipped with waterproof terminal boxes. Models marked VK..R are supplied with the power cord and a plug.
Motor
A centrifugal impeller with backward curved blades is powered by a single-phase external rotor motor. The motor is equipped with self-resetting overheating protection. Some standard sizes are available with a high-powered motor, see modification VKS.
The motor is equipped with ball bearings for a long service life designed for at least 40 000 operating hours. For precise features, safe operation and low noise, each impeller is dynamically balanced while assembly. Motor protection rating is IP 44.
Speed control
Smooth or step speed control with a thyristor or autotransformer speed controller. Several fans may be connected to one speed controller provided that the total power and operating current do not exceed the rated speed controller parameters.
Mounting
The fan is mounted to the wall or ceiling with mounting brackets included into delivery set or with PVK holders, specially ordered accessory. The fan can be mounted at any angle.
Electric connection and installation shall be performed in compliance with the manual and the wiring diagram on the terminal box.
The fan with electronic temperature and control module (U option).
The ideal solution for ventilation of the premises requiring permanent temperature control, i.e. greenhouses. The fan with the electronic temperature and speed control module provides automatic control of the motor speed (air capacity) depending on air temperature in the air duct or in the room.
The front panel of the electronic module has the following control knobs:
- speed control knob for setting the motor speed;
- thermostat control knob for setting the temperature set point;
- thermostat indicator light.
The fan is available in two modifications:
- with the temperature sensor integrated inside the fan air duct (U/U1 option);
- with the external temperature sensor fixed on the cable, 4 m long (Un / U1n).
Control logic of the fan with the electronic temperature and speed control module.
Set the desired air temperature (thermostat set point) by turning the thermostat control knob. Set the required minimum impeller speed (air flow) by turning the speed control knob. The motor switches to maximum speed (maximum air flow) as the temperature reaches and exceeds the set temperature set point. The motor switches to the preset lower speed as the temperature drops down below the temperature set point. To avoid frequent motor speed switches when the air temperature in the duct is equal to the set temperature point, the speed switch delay is activated.
There are two switch delay patterns for various cases:
- The temperature sensor-based switch delay (U option): the motor switches to higher speed as the air temperature exceeds 2 °C above the set thermostat set point. The motor revers to the preset lower speed as the air temperature drops below the thermostat set point. This pattern is used to keep air temperature to within 2 °C. In this case the motor speed switches are rare.
- The timer-based switch delay (U1 option): as the air temperature exceeds the set thermostat set point, the motor switches to higher speed and the switch delay timer is activated for 5 min. The motor reverts to lower speed as the air temperature drops down below the thermostat set point and only after 5 minuts timer countdown.
This pattern is used for exact air temperature control. The speed switches for the fan with U1 option are more frequent as compared to the operating logic of the fan with U option, however the minimum operating cycle at one speed is 5 minutes.
VENTS VK fan kitchen exhaust ventilation example
Example for temperature sensor delay pattern: |
Example for timer delay pattern: |
Initial conditions:
|
Initial conditions:
|
Motor operates with the rated speed =60% | Motor operates with the rated speed =60% |
↓
|
↓
|
|
|
↓ | ↓ |
| fan switches to the maximum speed =100% and the delay timer switches for 5 minutes again on |
↓ | ↓ |
|
|
↓ | ↓ |
|
|
↓ | |
after the timer stops, the motor switches to the preset rated speed (=60%). After the speed switch the timer switches again for 5 minutes on. | |
↓ | |
| |
↓ | |
after the timer stops, the motor switches to the maximum speed (=100%). After the speed switch the timer switches again for 5 minutes on. | |
Thus, in timer delay pattern the delay timer activates every time the fan speed changes |
Phohe