VA 01

VA 01

Compact suspended sound-insulated fan unit is designed to provide exhaust air removal from premises. Maximum capacity - 1400 m3/h.

Products in this series  (3)

  • VA 02

    VA 02

    VA 03

    VA 03

    VA 04

    VA 04

  • SKRA series

    SKRA series

  • Frequency speed controller VFED-…-TA

    Frequency speed controller VFED-…-TA

  • SR series (rectangular)

    SR series (rectangular)

  • FB series (rectangular)

    FB series (rectangular)

  • KOM1 series (rectangular)

    KOM1 series (rectangular)

  • VVG  series (rectangular)

    VVG series (rectangular)

  • BELIMO TF230/TF24

    BELIMO TF230/TF24

  • BELIMO LF230/LF24

    BELIMO LF230/LF24

  • FBK series (rectangular)

    FBK series (rectangular)

  • Three phase speed controller RSA5D-…-T

    Three phase speed controller RSA5D-…-T

  • Three phase speed controller RSA5D-…-M

    Three phase speed controller RSA5D-…-M

  • KG series (rectangular)

    KG series (rectangular)


ParameterValueUnit
Phase
3
˜
Voltage
400
V
Frequency
50
Hz
Maximum fan power
320
W
Fan current
0.55
A
Maximum air capacity
1400
824,6
389,2
0,3892
23380
m³/h
CFM
l/s
m³/s
l/m
RPM
2700
min -1
Sound pressure level at 3 m
51
[dBA]
Casing material
aluzinc
Maximum transported air temperature
-25 +55
оC
Insulation
50 mm, mineral wool
Connected air duct size
400х200
mm
Weight
35
kg
Heater type
none
Unit size
01
ЕС- motor
no
Type
exhaust
Heat recovery
no
VA 01
SizesBB1B2B3HH1H2LL1
mm400420624585200220375660621

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Online form

Send a message center customer support.


By using this form you confirm that you have read and agree with the site condition and terms.
Send

Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 69 53 66 63 57 53 50 56 52
LwA to outlet dBA 75 56 69 67 71 63 64 65 57
LwA to environment dBA 58 32 47 48 51 44 46 49 40