Vote

Please evaluate our updated site user friendliness

Keep up with us

RSS Subscribe to blog
Vents.TV

Blog messages

Go to blog

MPA 2500 Е3

MPA 2500 Е3

Sound- and heat-insulated ventilation unit. Supplies fresh filtered air to the premise. Electric heater is used for the unit operation at low temperatures. Maximum capacity - 2500 m3/h.

Voltage / frequency:

OK

Products in this series  (5)

    • MPA 800 Е1

      MPA 800 Е1

      Maximum capacity - 800 m3/h.

      MPA 1200 Е3

      MPA 1200 Е3

      Maximum capacity - 1200 m3/h.

      MPA 1800 Е3

      MPA 1800 Е3

      Maximum capacity - 2000 m3/h.

      MPA 3200 Е3

      MPA 3200 Е3

      Maximum capacity - 3200 m3/h.

      MPA 3500 Е3

      MPA 3500 Е3

      Maximum capacity - 3500 m3/h.

    • SKRA series

      SKRA series

    • OKW series

      OKW series

    • OKF series

      OKF series

    • USWK series

      USWK series

    • SR series (rectangular)

      SR series (rectangular)

    • VVG  series (rectangular)

      VVG series (rectangular)

    • BELIMO TF230/TF24

      BELIMO TF230/TF24

    • BELIMO LF230/LF24

      BELIMO LF230/LF24


    ParameterValueUnit
    Phase
    3
    ˜
    Voltage
    400
    V
    Frequency
    50
    Hz
    Maximum fan power
    650
    W
    Electric heater power
    18000
    W
    Electric heater current
    26
    A
    Fan current
    2.84
    A
    Total unit power
    18650
    W
    Total unit current
    28.84
    A
    Maximum air capacity
    2500
    1472,5
    695
    0,695
    41750
    m³/h
    CFM
    l/s
    m³/s
    l/m
    RPM
    1000
    min -1
    Sound pressure level at 3 m
    45
    [dBA]
    Casing material
    aluzinc
    Maximum transported air temperature
    -25 +45
    оC
    Insulation
    25 mm, mineral wool
    Filter
    G4
    Connected air duct size
    500х300
    mm
    Weight
    62
    kg
    Heater type
    electric
    ЕС- motor
    no
    Type
    supply
    Heat recovery
    no
    MPA 2500 Е3
    SizesBB1B2B3HH1H2LL1
    mm500520649600300320480800680

    E-mail

    Please, feel free to contact us.

    support@vents.ua

    Phohe

    Customer service.

    +380 44 406 36 25

    Online form

    Send a message center customer support.


    By using this form you confirm that you have read and agree with the site condition and terms.
    Send

    Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

    Sound-power level   Octave-frequency band [Hz]
      Hz   General   63   125   250   500   1000   2000   4000   8000
    LwA to inlet   dBA 79 82 80 80 70 70 66 66 58
    LwA to outlet dBA 82 82 84 79 75 79 74 71 68
    LwA to environment dBA 55 67 68 61 54 48 45 40 37