Vote

How often do you use equipment selection program?

Keep up with us

RSS Subscribe to blog
Vents.TV

Blog messages

Go to blog

MPA 3500 W

MPA 3500 W

Sound- and heat-insulated ventilation unit. Supplies fresh filtered air to the premise. Water heater is used for the unit operation at low temperatures. Maximum capacity - 3250 m3/h.

Voltage / frequency:

OK

Products in this series  (6)

    • MPA 800 W

      MPA 800 W

      Maximum capacity - 750 m3/h.

      MPA 1200 W

      MPA 1200 W

      Maximum capacity - 1200 m3/h.

      MPA 1800 W

      MPA 1800 W

      Maximum capacity - 1870 m3/h.

      MPA 2500 W

      MPA 2500 W

      Maximum capacity - 2150 m3/h.

      MPA 3200 W

      MPA 3200 W

      Maximum capacity - 3000 m3/h.

      MPA 5000 W

      MPA 5000 W

      Maximum capacity - 6500 m3/h.

    • SKRA series

      SKRA series

    • OKW series

      OKW series

    • OKF series

      OKF series

    • USWK series

      USWK series

    • SR series (rectangular)

      SR series (rectangular)

    • VVG  series (rectangular)

      VVG series (rectangular)

    • BELIMO TF230/TF24

      BELIMO TF230/TF24

    • BELIMO LF230/LF24

      BELIMO LF230/LF24


    ParameterValueUnit
    Phase
    3
    ˜
    Voltage
    400 Y
    V
    Frequency
    50
    Hz
    Maximum fan power
    1270
    W
    Fan current
    2.3
    A
    Total unit power
    1270
    W
    Total unit current
    2.3
    A
    Maximum air capacity
    3250
    1914,25
    903,5
    0,9035
    54275
    m³/h
    CFM
    l/s
    m³/s
    l/m
    RPM
    1200
    min -1
    Sound pressure level at 3 m
    53
    [dBA]
    Casing material
    aluzinc
    Maximum transported air temperature
    -40 +45
    оC
    Insulation
    25 mm, mineral wool
    Filter
    G4
    Connected air duct size
    600х350
    mm
    Weight
    73.1
    kg
    Number of water (glycol) coil rows
    4
    High-powered motor
    no
    Heater type
    water
    ЕС- motor
    no
    Type
    supply
    Heat recovery
    no
    MPA 3500 W
    SizesBB1B2B3HH1H2LL1L2
    mm6006207597103503705301000880440

    E-mail

    Please, feel free to contact us.

    support@vents.ua

    Phohe

    Customer service.

    +380 44 406 36 25

    Online form

    Send a message center customer support.


    By using this form you confirm that you have read and agree with the site condition and terms.
    Send

    Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

    Sound-power level   Octave-frequency band [Hz]
      Hz   General   63   125   250   500   1000   2000   4000   8000
    LwA to inlet   dBA 84 84 86 85 77 76 73 71 69
    LwA to outlet dBA 84 83 84 83 82 80 72 75 73
    LwA to environment dBA 60 67 66 71 54 55 50 45 45